Alarm delay
An alarm can become effective with a delay: the alarm output is set only after elapse of the adjusted
delay time, provided that the limit value is still exceeded. Shorter alarms than the adjusted delay are
ignored.
Signal change monitoring
Another limit value processing function is signal change monitoring (per minute).
Functions
SG 45
Limit value processing
30
Example: Alarm delay
LED
rot / red
t [min]
x
LED
rot / red
>
H.1
{
{
x
t
>
H.1
{
{
x
t
Lim.1
Behaviour with signal change (Ex. Lim1)
L.1
=
OFF