7.3
Configurations
Dependent on device version und adjusted configurations values not needed become hidden.
µ
Entrys marked with this symbol are selectable only with existing device-option.
Selection of functions Func
Name
Value range
Description
Fnc1
Function 1
0
No function
1
Zero setting
Fnc.2
Function 2
0
No function
3
Tare
Fnc.3
Function 3
0
No function
2
Sample & Hold
3
Integrator
Input INP
Name
Value range
Description
S.tYp
Sensor type
60
0,5 mV/V
61
1 mV/V
62
2 mV/V
63
4 mV/V (the selection for sensors with 3,33mV/V)
S.Lin
Linearization
0
No linearization
1
Special linearization
In.F
Alternative value
Limit values Lim1 … Lim3
Name
Value range
Description
Fnc.1
(
Fnc.2
)
(
Fnc.3
)
Function of limit 1 (2, 3)
0
Switched off
1
Measurement value
2
Measured value moni alarm status latch. A stored limit value can be reset
via error list or a digital input (
®
LOGI
/
Err.r
).
3
Signal change (in minutes).
4
Signal monitoring for rate of change (per minute) + storage of the alarm status. A sto-
red limit value can be reset via error list or a digital input (
®
LOGI
/
Err.r
).
Src.1
(
Src.2
)
(
Src.3
)
Source of limit 1 (2, 3)
0
process value = displayed value
3
Measured value INP
12
Zero offset (difference between the calibrated zero and the value at the time of
zero setting)
C.Std
OFF; 1 …
9999999
Control operating hours (only visible with BlueControl
Ò
!)
C.Sch
OFF; 1 …
9999999
Control switching cycles (only visible with BlueControl
Ò
!)
Configuration level
39
Configurations
SG 45