background image

for a specific control task can be

determined without a detailed study of

the operating instructions.

Off cause almost all adjustments can be

done comfortably over the instrument

front. (see page 7, BlueControl)

Password protection

If required, access to the various

operating levels can be protected with a

password. Similarly, access to a

complete level can be blocked.

TECHNICAL DATA

INPUTS

SURVEY OF THE INPUTS

Input

Used for:

INP1

x (process value)

INP2

Heating current, ext. set-point

di1

Operation disabled, switch-over

to second set-point SP.2,

external set-point SP.E, fixed

correcting variable Y2, manual

operation, controller off, disable

auto/manual function, reset of

stored alarms, boost, parameter

set 1

2

di2 (option)
di3 (option)

PROCESS VALUE INPUT INP1

Resolution:

> 14 bit

Decimal point:

0 to 3 decimals

Limiting frequency: 2 Hz
Digital input filter: adjustable 0,000...9999 s
Scanning cycle:

100 ms

Measured value

correction:

2-point or offset correction

Thermocouples

(Table 1)

Input impedance:

1 M

Effect of source resistance:

1

µ

V/

Cold junction compensation

Max. additional error

±

0,5 K

Sensor break monitoring

Sensor current:

1

µ

A

Operating sense configurable (see page 4)

Resistance thermometer

Connection:

3-wire

Lead resistance:

max. 30

Input circuit monitor:

Break and short circuit

Resistance measuring range

The BlueControl software can be used to

match the input to the sensor KTY 11-6

(characteristic is stored in the controller).

Physical measuring range:

0...4500

Linearization segments

16

2

KS 50-1

96

(3.78”)

48

(1.89”)

min.

48

(

1.89’’)

10

(0.4”)

1...10

0.04-0.4”

118

(4.65”)

45

+0,6

(1.77” )

+0 .0 2

125

126

SP.X

run

Err

Ada

92

+0,8

(3.62’

)

+0

.03

KS 50-1

universal

Dimensions (mm):

U

Logic

di2

di3

U

T

Option

RXD-B

GND

RXD-A

TXD-B

TXD-A

RS485

RS422

Modbus RTU

RGND

DATA B

DATA A

L

N

90...250V

24V AC/DC

+24V DC

24V GND

mA

mA

0..10 V*

HC

di1

INP1

INP2

OUT3

OUT2

OUT1

1

2
3

4

7

5

8

6

9

10

11

12
13
14
15

1

3
4
5
6
7
8
9

10
11
12
13
14
15

17

(2)

(16)

OUT5

OUT6

Electrical connections:

* Pay attention to the internal switch!

Safety isolation
Functional isolation

Mains supply

Process value input INP1
Supplementary input INP2
Digital input di1

Relay outputs OUT1,2 RS 422/485 interface
Relay output OUT3

Digital inputs di2, 3
Universal output OUT3
Transmitter supply U

T

OUT5, OUT6

Galvanic isolations:

Thermocouple

Range

Accuracy

Resolution (

)

L

Fe-CuNi (DIN)

-100...900 °C

-148...1652 °F

2 K

0,1 K

J

Fe-CuNi

-100...1200 °C

-148...2192 °F

2 K

0,1 K

K

NiCr-Ni

-100...1350 °C

-148...2462 °F

2 K

0,2 K

N

Nicrosil/Nisil

-100...1300 °C

-148...2372 °F

2 K

0,2 K

S

PtRh-Pt 10%

0...1760 °C

32...3200 °F

2 K

0,2 K

R

PtRh-Pt 13%

0...1760 °C

32...3200 °F

2 K

0,2 K

special

-25 ...75 mV

0,1 %

0,01 %

Table 1 Thermocouple ranges

Type

Sensor current

Range

Accuracy

Resolution (

)

Pt100

0,2 mA

-200...850 °C

-328...1562 °F

1 K

0,1 K

Pt1000

-200...200 °C

-328...392 °F

2 K

0,1 K

Resistance

*

4500

0,1 %

0,01 %

* The characteristic of a KTY 11-6 is preadjusted (-50...150°C)

Table 2 Resistance transducers

Range

Input resistance

Accuracy

Resolution (

)

0-10 Volt

110 k

0,1 %

0,6 mV

0-20 mA

49

(voltage requirement

2,5 V)

0,1 %

1,5

µ

A

Table 3 Current and voltage

Summary of Contents for KS 50-1

Page 1: ...tion start up ensure increased lifetime of high performance electrical heating elements e g hot runner moulds Plug in module KS 50 1 controllers are built as plug in modules This enables them to be re...

Page 2: ...stored in the controller Physical measuring range 0 4500 Linearization segments 16 2 KS 50 1 96 3 78 48 1 89 min 48 1 89 10 0 4 1 1 0 0 0 4 0 4 118 4 65 45 0 6 1 77 0 0 2 125 126 SP X run Err Ada 92 0...

Page 3: ...oint control deviation transmitter supply 13 V 22 mA OUT5 OUT6 Optocoupler as OUT1 and OUT2 OPTION All logic signals can be OR linked RELAY OUTPUTS OUT1 OUT2 Contacts 2 NO contacts with common connect...

Page 4: ...tched off Switch over to a safe output value Switch over to a mean output value PID controller SP setpoint power on disturbance t SP St process value Start up circuit When the process is controlled to...

Page 5: ...ection if there is no response of the process to a change of output value Sensor break or short circuit Depending on selected input type the input signal is monitored for break and short circuit MAINT...

Page 6: ...tion 20 65 C For storage 40 70 C Humidity 75 yearly average no condensation Shock and vibration Vibration test Fc DIN 68 2 6 Frequency 10 150 Hz Unit in operation 1g or 0 075 mm Unit not in operation...

Page 7: ...inputs outputs Forcing allows to write the analog and digital inputs and outputs via Modbus interface Adjustment of limits for operating hours and switching cycles Switch over to 60 Hz mains frequenc...

Page 8: ...to specification 9 no manual 0 manual german D manual english E manual french F Standard 0 UL certified U DIN 3440 certified D ORDERING INFORMATION Description Order no Current converter 50A AC 9404 4...