Plymovent DRAFTMAX BASIC Installation And User Manual Download Page 12

0507060400/010920/M DraftMax Basic | DraftMax Ultra 

11

Fig. 4.22 Mounting of the bench vice mounting bracket

4.4.12  Wheel set

 

Swivel caster with brake (2)

 

Swivel caster without brake (3)

To install the wheet set, do the following.

•  Lift the downdraft table with a fork-lift truck or pallet truck.
•  Loosen and remove the 5 adjusting feet.
•  Install the swivel casters instead; 

 

- swivel casters with brake: left + right front corner

 

- swivel casters without brake: positions on the rear

ATTENTION

Turn the screw thread of the swivel casters in as 

deep as possible.
By the use of the wheelset, the working height of 

the downdraft table is fixed to 950 mm (37½ in.).

4.5 

Work grid

To install the work grid, do the following.

Fig. 4.1

•  Loosen the ground bracket

3

 from the downdraft table. Keep 

the screws.

•  Install the work grids.

•  Put the ground bracket over both work grids.

•  Attach it with the removed screws.

Fig. 4.1  Ground bracket (two-piece)

3.  The ground bracket consists of two pieces

ATTENTION

It is necessary to apply the bracket to ground the 

work grids.

4.6 

Compressed air connection  

(DraftMax Ultra only)

The downdraft table functions on compressed air 

with a recommended working pressure of 5-8 bar 

(72-115 psi). Make sure that the working pressure is between 

these values (preferably at 5 bar/72 psi). If required, install a 

pressure relief valve to prevent overpressure. If the pressure 

is too high, the pressure relief valve of the system will be 

opened, thus decreasing the pressure until the system 

pressure has reached an appropriate level.

ATTENTION

The compressed air must be dry and oil-free 

according to ISO 8573-3 class 6.

•  Connect the downdraft table to compressed air (refer to 

Fig. 2.3C).

4.7 

Positioning

You can move the downdraft table to its final 

position with:

 

- a fork-lift truck (preferred way); or

 

- a pallet truck (in this case you must tilt the table); or

 

- cargo lashings lifted by a fork-lift truck (refer to Fig. I on 

page 17)

CAUTION

Do not position the product where it is exposed to 

vibrations or heat radiation from heat sources. 

Observe the earlier described ambient conditions.

•  Put the downdraft table against the wall. 
•  If necessary: 

Use the adjusting feet to put the table level and to adjust it 

to the desired height (min. 920 mm - max. 970 mm/36-38 

in.) (also refer to Fig. III on page 17).

4.8 

Electric connection

CAUTION

Make sure that the product is suitable for connection 

to the local mains. You can find information about 

the connection voltage and frequency on the 

identification plate. 

The cables must be connected in conformance with 

the local rules and regulations and can only be 

carried out by well qualified and authorised 

technicians.

You can connect the downdraft table to the mains by:

 

- a three-phase plug (grounded); or 

 

- directly to the power supply

•  Connect the mains cord to the mains.

4.8.1  Sense of rotation

To make sure that the sense of rotation of the fan is correct:

•  Turn on the main switch. 

•  Push the ON button to switch on the fan. 

• 

Push the OFF button to switch off the fan. 

•  Wait 10 seconds. 

•  Open the left door.

Summary of Contents for DRAFTMAX BASIC

Page 1: ...www plymovent com Downdraft table DRAFTMAX BASIC ULTRA Installation and user manual EN...

Page 2: ...y serve as a guideline for installation use maintenance and repair of the product mentioned on the cover page of this document This publication is to be used for the standard model of the product of t...

Page 3: ...1 2 General description The downdraft table is a workbench with an integrated extraction fan and filtration system that is used for welding grinding and plasma cutting applications Depending on the sp...

Page 4: ...wer consumption 2 2 kW 3 HP Mains cord 3 m 10 ft 1 m 3 ft internal 2 m 6 ft external without plug Protection class IP 55 control box only Sound level according to ISO 3746 without options with silence...

Page 5: ...welding and plasma cutting applications and recommended for grinding applications By the use of a backdraft kit the downdraft extraction capacity is reduced to approx 20 The remaining 80 is extracted...

Page 6: ...d not to play with the product Intended use2 The product has been designed as a workbench with integrated extraction and filtration facility for welding and grinding purposes provided the appropriate...

Page 7: ...xtinguishers suitable for fire classes ABC Service maintenance and repairs Obey the maintenance intervals given in this manual Overdue maintenance can lead to high costs for repair and revisions and c...

Page 8: ...e panel Right side panel To install the side panels do the following Fig 4 7 Loosen the bolts on the loose side of the hinges and remove the washers Keep the bolts and washers Put the pins through the...

Page 9: ...owndraft table Keep the 4 bolts Apply the draught strip A to the downdraft table Fig 4 11 A Draught strip Fig 4 12 Push a screwdriver or other tool at the position of the strips B to unlock the HEPA f...

Page 10: ...e Silencer Outlet duct do the following Fig 4 14 If applicable remove the outlet panel of the downdraft table or the outlet panel of the HEPA box Keep the 4 bolts Apply the draught strip to the downdr...

Page 11: ...l the movement sensor on top of the back panel or backdraft panel with the 2 bolts A Fig 4 20 A x2 Mounting of the movement sensor Fig 4 21 Lead the cable down the back side of the downdraft table Att...

Page 12: ...e system will be opened thus decreasing the pressure until the system pressure has reached an appropriate level ATTENTION The compressed air must be dry and oil free according to ISO 8573 3 class 6 Co...

Page 13: ...welding grinding Push the OFF button D after you have finished welding grinding to stop the fan 5 1 3 Filter replacement Fig 5 1 During use you must regularly check the pressure gauge B When the pres...

Page 14: ...ution and carry out the maintenance at regular intervals any problems occurring will be detected and corrected before they lead to a total breakdown WARNING Overdue maintenance can cause fire The indi...

Page 15: ...astic bag and comes with face mask and a pair of disposable gloves You must replace the HEPA filter together with the filter cartridges To replace the HEPA filter do the following Open the door of the...

Page 16: ...leaned One of the membrane valves defective Replace both membrane valves Poor extraction capacity No filter cleaning Membrane valve s defective Replace both membrane valves Button MANUAL CLEANING does...

Page 17: ...our own responsibility that the product DraftMax Basic DraftMax Ultra which this declaration refers to is in accordance with the conditions of the following Directives Machine Directive 2006 42 EC EM...

Page 18: ...ion option option no Wheel set option option option option Dust tray lid recommended recommended option option DraftMax Ultra yes yes yes yes Back panel no no option option Backdraft kit required requ...

Page 19: ...240 0000101408 0040900020 0040000040 0000102289 0328400130 0040900220 0000101348 0040900080 0040900090 0040900050 0040900060 0040900270 2x 0040000020 0040100060 0046030010 0040000030 0000110543 004090...

Page 20: ...HP 208 240 480V 3ph 60Hz USA 0040900090 Motor downdraft table 3 kW 4 HP 600V 3ph 60Hz Canada 0040900120 Push button black 0040900130 Push button green incl LED 0040900180 Main switch 25A 0040900220 T...

Page 21: ...www plymovent com 0507060400 010920 M DraftMax Basic DraftMax Ultra...

Reviews: