Plum ecoMAX920P1-S TOUCH Installation And Operating Manual Download Page 39

39 

 

14.4

 

Buffer 

Parameter 

Description 

Buffer support 

Parameter  serves  to  activate  buffer  operating  mode.  It  is  available  after  connecting  additional 
module B and buffer temperature sensors. 

Buffer loading start 
temperature 

Parameter 

Buffer loading start temperature 

defines the upper temperature of the buffer below which 

the  buffer  loading  process  starts.  Buffer  loading  process  is  ended  when  lower  buffer  temperature 
reaches value defined by parameter 

Buffer loading end temperature

Buffer loading end 
temperature 

14.5

 

Mixer 

Parameter 

Description 

Thermostat selection 

Parameter available only after connecting room panel. Option enables changing room thermostat for 
mixer circuit. 
Available options:  

 

Off 

– turns off the influence of room thermostat on mixer circuit operation, 

 

Universal 

– turns on standard room thermostat for mixer circuit, 

 

ecoSTER  T1..T3

, eSTER  T1…T3   – option available after connecting room panel and makes 

mixer  circuit  operation  dependent  on  the  thermostat  in  room  panel.  If  room  panel  is 
disconnected the controller operates only with standard room panel. 

Mixer support

 

 

Off 

Mixer servomotor and mixer pump are not operating. 

 

CH on 

It applies when mixer circuit supplies CH heating installation. Maximum mixer circuit temperature is 
not  limited,  mixer  is  fully  open  during  alarms,  e.g.  boiler  overheat.  Attention:  do  not  enable  this 
option  when  installation  is  made  of  pipes  sensitive  to  high  temperature.  In  such  situations  it  is 
recommended to set 

Mixer support 

to 

Floor on.

 

 

Floor on 

It applies when mixer circuit supplies floor installation. Maximum mixer circuit temperature is limited 
to  the  value  of 

Max.  preset  mixer  temp. 

parameter.  Attention:  after  selecting  option 

Floor  on 

the 

parameter 

Max. mixer temp. 

must be set to such value, so that the floor was not damaged and there 

was no risk of scalding. 

 

Pump only 

When mixer circuit temperature exceeds temperature set in 

Mixer preset temperature 

the supply of 

mixer  pump  will  be  off.  After  decreasing  circuit  temperature  by 

2ºC  –  pump  is switched  on  again. 

This option is usually used to control floor heating pump when it cooperates with thermostatic valve 
without servomotor. However, such action is not recommended. It is recommended to use standard 
heating circuit for floor heating, consisting in valve, servomotor and mixer pump. 

Minimum mixer 
temperature 

It is a parameter with which user can be limited from setting too low preset mixer circuit temperature. 
Automatic regulation (e.g. temporary temperature decrease) also will not cause decreasing of preset 
temperature value below value set in this parameter. 

Maximum mixer 
temperature 

The parameter has two functions: 
 -  enables  limiting  setting  too  high  preset  mixer  temperature  by  the  user.  Automatic  regulation 
(correction  according  to  heating  curve  from  outside  temperature)  also  will  not  cause  exceeding 
preset temperature over the value set in this parameter. 
- with parameter 

Mixer support

 = 

Floor on 

is at the same time the limit temperature of mixer sensor 

at which mixer pump will be off. For floor heating set the value not greater than  45-

50°C or other if 

the  manufacturer  of  materials  used  to  construct  the  floor  or  CH  installation  designer  specified 
otherwise. 

Valve opening time 

Enter 

Full valve opening time 

value read from servomotor’s nameplate, e.g. 140 sec. 

Pump off by 
thermostat 

Setting parameter to 

YES 

will close the mixer servomotor and switch off mixer pump after opening 

room  thermostat  contacts  (room  heated).  However  this  action  is  not  recommended  as  the  heated 
room may be still cold. 

Mixer dead zone 

Parameter  setting  determining  temperature  dead  zone  value  for  the  mixer  control  system.  The 
controller controls the mixer so that the temperature value measured by the mixer circuit sensor was 
equal to the preset value. However to avoid too frequent servomotor movement, that can shorten its 
lifetime, the control is initiated only when the measured mixer circuit temperature is higher or lower 
from the preset by the value greater than 

Mizer dead zone.

 

 

Summary of Contents for ecoMAX920P1-S TOUCH

Page 1: ...TALLATION AND OPERATING MANUAL ISSUE 1 0_EN Functions available in additional module B ecoSTER TOUCH ecoNET300 ecoNET apk ecoNET app www econet24 com Devices are not standard equipment of the controll...

Page 2: ...eam condensation conditions and cannot be exposed to water MAIN PRINCIPLES OF PROPER BOILER OPERATION WITH INDIVIDUAL FUZZY LOGIC The controller must be programmed individually for a given boiler and...

Page 3: ...ROTECTION LEVEL 24 12 5 ELECTRIC CONNECTION 24 12 6 ELECTRIC SCHEME 26 12 7 CONNECTION OF TEMPERATURE SENSORS 28 12 8 CONNECTING THE WEATHER TEMP SENSOR 28 12 9 CONNECTING THE EXHAUST TEMPERATURE SENS...

Page 4: ...is intended for boiler manufacturers Before applying the controller a boiler manufacturer should check if the controller s matching with the given boiler type is proper and whether it can cause dange...

Page 5: ...bserve these instructions 4 Storage of documentation This assembly and operation manual as well as any other applicable documentation should be stored diligently so that it was available at any time I...

Page 6: ...6...

Page 7: ...USER SETTINGS ecoMAX920P1 S TOUCH...

Page 8: ...n Decrease value Schedule Night time circ pump decrease Summer Winter SUMMER mode Summer Winter Auto SUMMER mode activation temp SUMMER mode deactivation temp Mixer 1 5 settings 5 Preset mixer tempera...

Page 9: ...10 Functions affecting preset boiler temperature Following symbols signal respectively room thermostat contacts open preset room temperature reached preset boiler temperature decrease due to activated...

Page 10: ...er e g boiler inactivity period in STOP mode Fan is switched on with the power set by Firing up airflow parameter Small fuel dosage is given 20 of basic dosage If during period set by Ignition test ti...

Page 11: ...teresis H2 and 30 H1 hysteresis Hysteresis H1 and H2 of power modulation Operation in Fuzzy Logic mode In Fuzzy Logic mode the controller automatically regulates burner power to allow boiler operation...

Page 12: ...ng the fuel and performs cyclic blowing according to Blowing time and Blowing pause settings in order to burn the remaining fuel After flame brightness dropping below Burning out end threshold value i...

Page 13: ...the menu Summer Winter SUMMER mode for Summer Attention when boiler operates without heating buffer and the controller is switched into SUMMER mode than Standard mode operation is recommended It is no...

Page 14: ...m temperature 18 C the controller will move heating curve by 2 C In some cases described in point 8 18 it can be necessary to adjust heating curve shift In this configuration room thermostat is able t...

Page 15: ...oiler Time periods allow setting temperature reduction in given time period i e at night or when user leaves the heated room Thanks to it preset temperature can be reduced automatically without loss o...

Page 16: ...Fuel level 0 There is a possibility to skip the calibration process if the parameters are set correctly Feeder efficiency and Capacity of tank which are in Service settings Burner settings Operation 8...

Page 17: ...er operation status alarms allows to set controller parameters and its operation modes it also serves as an additional panel controlling the boiler 8 26 Cooperation with internet module The controller...

Page 18: ...18...

Page 19: ...19 INSTALLATION AND SERVICE SETTINGS ecoMAX920P1 S TOUCH...

Page 20: ...c If the return sensor is clip on insulate it thermally from the surroundings and improve thermal contact with the pipe by using thermal grease Boiler s preset temperature must be set high enough to p...

Page 21: ...te 80 C Boiler settings Minimum boiler temperature 75 C Service settings Boiler settings CH pump activation temperature 55 C Service settings CH and HUW settings Buffer support Yes Service settings Bu...

Page 22: ...gs Buffer settings Buffer loading start temperature 50 C Service settings Buffer settings Buffer loading end temperature 75 C Service settings Buffer settings Mixer 1 2 3 4 support CH on Service setti...

Page 23: ...ontroller 5 IP20 from the front side of the executive module IP00 from the side of the executive module cover against damage to the STB capillary placed in the terminal box 12 Controller installation...

Page 24: ...ction device RCD with inrush current I n 30 mA protecting against the effects of the regulator including protection against fire After deactivating the controller there still can be a dangerous voltag...

Page 25: ...from the casing of the controller as shown below Cables secured from splitting should be connected to screw terminals of the 6 connector Cables should be put through cable outlets in the casing 1 and...

Page 26: ...otor AS ash removal servomotor RT room panel or ISM radio module Lambda probe module B module to support additional heating circuits BT boiler temp sensor type CT4 FS feeder temp sensor type CT4 RS bo...

Page 27: ...rcuit temp sensor type CT4 T3 buffer upper temp sensor type CT4 T4 buffer lower temp sensor type CT4 LS fuel level sensor cooperating with bunker feeder T standard mixer room thermostat H voltage outp...

Page 28: ...between these wires should be 100 mm Do not allow sensor wires to contact hot parts of the boiler and heating system Wires of temperature sensors are heat resistant to the temperature not exceeding 1...

Page 29: ...2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S Pt1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8...

Page 30: ...al module B Exemplary wiring diagram for connecting auxiliary boiler to the controller 1 additional module B 2 auxiliary boiler gas or oil 3 relay RM 84 2012 35 1006 and base GZT80 RELPOL By standard...

Page 31: ...enu Service settings Boiler settings Auxiliary boiler and set zero value for its switching on temperature Exemplary external alarm device connection 1 additional module B 2 external alarm device 3 rel...

Page 32: ...s power indicator of valve opening has been calibrated Attention in mixers 2 3 4 5 the calibration is automatic after switching on the mains power In case of these mixers wait until indicator of valve...

Page 33: ...hich is not the controller s equipment Connect D D wires to G3 socket in the controller Maximum cables length to room panel depends on wires cross section and for 0 25 mm2 wire it should not exceed 30...

Page 34: ...wer increasing Stoker emptying time Cycle Poker operation time Poker pause Stoker emptying time Roto Poker operation time Poker pause Stoker emptying time Cycle x K Poker operation time Poker pause Po...

Page 35: ...ing start temperature Buffer loading end temperature Mixer 1 5 settings Thermostat selection Mixer support OFF CH ON Floor ON Only pump Minimum mixer temperature Maximum mixer temperature Proportional...

Page 36: ...ng the fuel Feeder 2 minimum time Minimum operation time for feeder placed in burner Feeder 2 operation time Determines operation time of additional feeder bunker feeder The feeder is connected to add...

Page 37: ...ted after finishing of which it will start operation again increasing the device s power to preset operation conditions Mechanism 2 when the burner finishes its operation in Burning out Burning off mo...

Page 38: ...lt in excessive CH installation cooling since with such settings CH pump is off CH pump standstill parameter during HUW loading prevents it by enabling periodical CH pump activation during loading of...

Page 39: ...eset temperature the supply of mixer pump will be off After decreasing circuit temperature by 2 C pump is switched on again This option is usually used to control floor heating pump when it cooperates...

Page 40: ...ue to 0 switches alarm off Outputs test time After this time all devices that were switched ON in Manual control menu will be switched off automatically Show advanced Available options YES displays hi...

Page 41: ...lame striking back will be off in this case Protective function against flame strike back does not work when feeder sensor is disconnected or when it s damaged or when the controller is not supplied T...

Page 42: ...the form of two files file with panel program and a file with program for module A of the controller Place new firmware directly on the memory card do not place data in a folder Then connected electri...

Page 43: ...necessary information read from nameplates In case of the controller it is essential to know its serial number If the serial number is unknown provide its model design and year of production Controlle...

Page 44: ...and the fuel is not provided check the feeder according to its manual Fuel feeder not operating does not provide fuel Check if feeder wires are correctly connected to terminals If STB temperature lim...

Page 45: ...45...

Page 46: ...46...

Page 47: ...47...

Page 48: ...48 ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www plum pl National Waste Disposal No 000009381...

Reviews: