Installing the exhaust temp. sensor: 1 – exhaust temp.
sensor type CT2S, 2 – sensor lead, 3 – flue
.
Attention: Opening the boiler door
can
cause
the
emission
temperature to exceed the sensor‘s
thermal resistance, which can burn
the sensor out.
12.10
Temperature sensors checking
Temperature sensors can be checked by
measuring
their
resistance
in
given
temperature. In case of big differences
between measured resistance value and
values in table below, the sensor should be
replaced with a new one.
CT4 (KTY81)
Ambient
Temp. °C
Min.
Ω
Nom.
Ω
Max.
Ω
0
802
815
828
10
874
886
898
20
950
961
972
25
990
1000
1010
30
1029
1040
1051
40
1108
1122
1136
50
1192
1209
1225
60
1278
1299
1319
70
1369
1392
1416
80
1462
1490
1518
90
1559
1591
1623
100
1659
1696
1733
CT6-P (PT1000) - weather
Temp.
°C
Min.
Ω
Nom.
Ω
Max.
Ω
-25
901,6
901.9
1000,2
-20
921,3
921.6
921,9
-10
960,6
960.9
961,2
0
999,7
1000.0
1000,3
25
1096,9
1097.3
1097,7
50
1193,4
1194.0
1194,6
100
1384,2
1385.0
1385,8
125
1478,5
1479.4
1480,3
150
1572,0
1573.1
1574,2
CT2S (Pt1000) - exhaust
Temp.
°C
Min.
Ω
Nom.
Ω
Max.
Ω
0
999,7
1000.0
1000,3
25
1096,9 1097.3
1097,7
50
1193,4 1194.0
1194,6
100
1384,2 1385.0
1385,8
125
1478,5 1479.4
1480,3
12.11
Optical sensor connection
The controller cooperates only with sensor of
type OCP. The sensor must be connected
accordingly to the electrical scheme.
Indications reading from optical flame sensor
is enabled in the menu:
Information
→
Flame
Incorrect optical sensor connection
shall not damage the controller or
sensor itself, but burner flame
detection will be false.
12.12
Mixers room thermostat
connection
Room thermostat after disconnecting wires
reduces preset temperature of the value of
reduction the preset temperature of the
mixer from the thermostat. Parameter is in
the menu:
Mixer 1-5 settings
→
Mixer room
thermostat
Parameter value should be chosen in such a
way, that after activating the room
thermostat
(opening
contacts),
the
temperature in the room was dropping. In
case of connecting room panel make sure,
that the parameter Thermostat selection is
properly set in the menu:
220ºC