in  Fuzzy  Logic  regulation  mode  –  after 
exceeding  boiler  preset  temperature  by 
5ºC. 

In  SUPERVISION  mode  the  controller 
oversees  the  furnace,  keeping  it  from 
burning  off.  To  do  so,  the  burner  operates 
with  very  low  power,  what  together  with 
properly  adjusted  parameters  do  not  cause 
further  increase  in  temperature.  Burner’s 
power  in  SUPERVISION  mode    and  other 
parameters of Supervision are grouped in the 
menu: 
Service  settings 

  Burner  settings 

  

Supervision 
Mode  parameters  must  be  set  according  to 
recommendations 

of 

boiler/burner 

manufacturer.  They  should  be  selected  in 
such  a  way  that  the  furnace  did  not  damp 
out  during  boiler  pauses  (it  should  not  be 
fired  up  too  much  simultaneously  as  it  will 
cause boiler temperature to increase). 

 

 

The parameters in this mode must 
be so chosen as to make the boiler 
temperature  gradually  decreasing. 
Incorrect  settings  can  cause  boiler 
overheating.  

Maximum  time  of  boiler’s  operating  in 
supervision  mode  is  defined  in  service 
parameter Supervision time. If after this time 
(in  Supervision  mode)  there  is  no  need  to 
restart  the  boiler  then  the  controller  starts 
the process of boiler’s burning off. 

 

For setting Supervision time = 0 the 
controller  omits  SUPERVISION  mode 
and goes directly to BURNING OFF. 

8.9

 

BURNING OUT/BURNING OFF 

mode 

In  BURNING  OUT  mode  the  remaining  fuel 
burns  out  and  the  boiler  is  prepared  for 
burning  off  and  next  to  enter  STOP  or 
CLEANING  mode.  All  parameters  affecting 
the  burning  out/burning  off  process  are 
grouped in the menu: 
Service 

settings 

 

Burner  settings 

  Burning  out/Burning 

off 
The  controller  stops  feeding  the  fuel  and 
performs cyclic blowing according to Blowing 
time  
and  Blowing  pause  settings  in  order  to 
burn  the  remaining  fuel.  After  flame 

brightness  dropping  below  Burning  out  end 
threshold  
value  it  enters  into  Burning  off 
mode where after  expiry of  Burning off time 
the  controller  will  shut  down  the  boiler  but 
still control the CH and HUW pumps. 

8.10

 

STOP mode 

In  the  STOP  mode  the  boiler  is  being  burnt 
off  and  awaits  the  signal  to  start  operation. 
The  following  can  be  a  signal  to  start 
operation: 

 

decrease  of  preset  boiler  temperature 
below  preset  temperature  diminished  by 
boiler hysteresis  (Boiler hysteresis),  

 

by  boiler  operation  configuration  with  the 
buffer  decrease  of  top  buffer  temperature 
below  preset  value  (Buffer  loading  start 
temperature
). 

8.11

 

GRATE mode/CLEANING 

Some  boilers  have  an  additional  grate  to 
burn other fuels such as wood waste, etc. To 
activate  the  grate,  move  the  parameters 
available in the menu:  
Boiler  settings 

→ 

Operation  mode  from 

"pellet" to "grate".  
In  the  grate  mode  fuel  feeder  is  turned  off. 
The  combustion  process  is  regulated  by  the 
fan. Fan power, when working with grate, is 
set  in  the  parameters:  Fan  in  grate  mode
Fan output in grate mode and Blowing power 
–  supervision
,  Blowing  pause  -  maintaining
The parameters affecting the grate operation 
are set in the menu: 
Boiler settings 

→ 

Output modulation  

and 
Service  settings 

  Burner  settings 

→ 

Cleaning 
Service  settings 

  Burner  settings 

→ 

Grate 
The values of parameters such as: 
Boiler settings 

 CH preset temperature 

- grate 
Service  settings 

  Boiler  settings 

 

Boiler hysteresis - grate 
are individually adjusted for the "grate". This 
allows to define different properties of boiler 
operation  for  operation  modes  "grate"  and 
"pellets". When using the grate an alarm "No 
fuel
"  can  appear.  This  alarm  occurs  when  a 

Summary of Contents for ecoMAX920P1-S TOUCH

Page 1: ...TALLATION AND OPERATING MANUAL ISSUE 1 0_EN Functions available in additional module B ecoSTER TOUCH ecoNET300 ecoNET apk ecoNET app www econet24 com Devices are not standard equipment of the controll...

Page 2: ...eam condensation conditions and cannot be exposed to water MAIN PRINCIPLES OF PROPER BOILER OPERATION WITH INDIVIDUAL FUZZY LOGIC The controller must be programmed individually for a given boiler and...

Page 3: ...ROTECTION LEVEL 24 12 5 ELECTRIC CONNECTION 24 12 6 ELECTRIC SCHEME 26 12 7 CONNECTION OF TEMPERATURE SENSORS 28 12 8 CONNECTING THE WEATHER TEMP SENSOR 28 12 9 CONNECTING THE EXHAUST TEMPERATURE SENS...

Page 4: ...is intended for boiler manufacturers Before applying the controller a boiler manufacturer should check if the controller s matching with the given boiler type is proper and whether it can cause dange...

Page 5: ...bserve these instructions 4 Storage of documentation This assembly and operation manual as well as any other applicable documentation should be stored diligently so that it was available at any time I...

Page 6: ...6...

Page 7: ...USER SETTINGS ecoMAX920P1 S TOUCH...

Page 8: ...n Decrease value Schedule Night time circ pump decrease Summer Winter SUMMER mode Summer Winter Auto SUMMER mode activation temp SUMMER mode deactivation temp Mixer 1 5 settings 5 Preset mixer tempera...

Page 9: ...10 Functions affecting preset boiler temperature Following symbols signal respectively room thermostat contacts open preset room temperature reached preset boiler temperature decrease due to activated...

Page 10: ...er e g boiler inactivity period in STOP mode Fan is switched on with the power set by Firing up airflow parameter Small fuel dosage is given 20 of basic dosage If during period set by Ignition test ti...

Page 11: ...teresis H2 and 30 H1 hysteresis Hysteresis H1 and H2 of power modulation Operation in Fuzzy Logic mode In Fuzzy Logic mode the controller automatically regulates burner power to allow boiler operation...

Page 12: ...ng the fuel and performs cyclic blowing according to Blowing time and Blowing pause settings in order to burn the remaining fuel After flame brightness dropping below Burning out end threshold value i...

Page 13: ...the menu Summer Winter SUMMER mode for Summer Attention when boiler operates without heating buffer and the controller is switched into SUMMER mode than Standard mode operation is recommended It is no...

Page 14: ...m temperature 18 C the controller will move heating curve by 2 C In some cases described in point 8 18 it can be necessary to adjust heating curve shift In this configuration room thermostat is able t...

Page 15: ...oiler Time periods allow setting temperature reduction in given time period i e at night or when user leaves the heated room Thanks to it preset temperature can be reduced automatically without loss o...

Page 16: ...Fuel level 0 There is a possibility to skip the calibration process if the parameters are set correctly Feeder efficiency and Capacity of tank which are in Service settings Burner settings Operation 8...

Page 17: ...er operation status alarms allows to set controller parameters and its operation modes it also serves as an additional panel controlling the boiler 8 26 Cooperation with internet module The controller...

Page 18: ...18...

Page 19: ...19 INSTALLATION AND SERVICE SETTINGS ecoMAX920P1 S TOUCH...

Page 20: ...c If the return sensor is clip on insulate it thermally from the surroundings and improve thermal contact with the pipe by using thermal grease Boiler s preset temperature must be set high enough to p...

Page 21: ...te 80 C Boiler settings Minimum boiler temperature 75 C Service settings Boiler settings CH pump activation temperature 55 C Service settings CH and HUW settings Buffer support Yes Service settings Bu...

Page 22: ...gs Buffer settings Buffer loading start temperature 50 C Service settings Buffer settings Buffer loading end temperature 75 C Service settings Buffer settings Mixer 1 2 3 4 support CH on Service setti...

Page 23: ...ontroller 5 IP20 from the front side of the executive module IP00 from the side of the executive module cover against damage to the STB capillary placed in the terminal box 12 Controller installation...

Page 24: ...ction device RCD with inrush current I n 30 mA protecting against the effects of the regulator including protection against fire After deactivating the controller there still can be a dangerous voltag...

Page 25: ...from the casing of the controller as shown below Cables secured from splitting should be connected to screw terminals of the 6 connector Cables should be put through cable outlets in the casing 1 and...

Page 26: ...otor AS ash removal servomotor RT room panel or ISM radio module Lambda probe module B module to support additional heating circuits BT boiler temp sensor type CT4 FS feeder temp sensor type CT4 RS bo...

Page 27: ...rcuit temp sensor type CT4 T3 buffer upper temp sensor type CT4 T4 buffer lower temp sensor type CT4 LS fuel level sensor cooperating with bunker feeder T standard mixer room thermostat H voltage outp...

Page 28: ...between these wires should be 100 mm Do not allow sensor wires to contact hot parts of the boiler and heating system Wires of temperature sensors are heat resistant to the temperature not exceeding 1...

Page 29: ...2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S Pt1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8...

Page 30: ...al module B Exemplary wiring diagram for connecting auxiliary boiler to the controller 1 additional module B 2 auxiliary boiler gas or oil 3 relay RM 84 2012 35 1006 and base GZT80 RELPOL By standard...

Page 31: ...enu Service settings Boiler settings Auxiliary boiler and set zero value for its switching on temperature Exemplary external alarm device connection 1 additional module B 2 external alarm device 3 rel...

Page 32: ...s power indicator of valve opening has been calibrated Attention in mixers 2 3 4 5 the calibration is automatic after switching on the mains power In case of these mixers wait until indicator of valve...

Page 33: ...hich is not the controller s equipment Connect D D wires to G3 socket in the controller Maximum cables length to room panel depends on wires cross section and for 0 25 mm2 wire it should not exceed 30...

Page 34: ...wer increasing Stoker emptying time Cycle Poker operation time Poker pause Stoker emptying time Roto Poker operation time Poker pause Stoker emptying time Cycle x K Poker operation time Poker pause Po...

Page 35: ...ing start temperature Buffer loading end temperature Mixer 1 5 settings Thermostat selection Mixer support OFF CH ON Floor ON Only pump Minimum mixer temperature Maximum mixer temperature Proportional...

Page 36: ...ng the fuel Feeder 2 minimum time Minimum operation time for feeder placed in burner Feeder 2 operation time Determines operation time of additional feeder bunker feeder The feeder is connected to add...

Page 37: ...ted after finishing of which it will start operation again increasing the device s power to preset operation conditions Mechanism 2 when the burner finishes its operation in Burning out Burning off mo...

Page 38: ...lt in excessive CH installation cooling since with such settings CH pump is off CH pump standstill parameter during HUW loading prevents it by enabling periodical CH pump activation during loading of...

Page 39: ...eset temperature the supply of mixer pump will be off After decreasing circuit temperature by 2 C pump is switched on again This option is usually used to control floor heating pump when it cooperates...

Page 40: ...ue to 0 switches alarm off Outputs test time After this time all devices that were switched ON in Manual control menu will be switched off automatically Show advanced Available options YES displays hi...

Page 41: ...lame striking back will be off in this case Protective function against flame strike back does not work when feeder sensor is disconnected or when it s damaged or when the controller is not supplied T...

Page 42: ...the form of two files file with panel program and a file with program for module A of the controller Place new firmware directly on the memory card do not place data in a folder Then connected electri...

Page 43: ...necessary information read from nameplates In case of the controller it is essential to know its serial number If the serial number is unknown provide its model design and year of production Controlle...

Page 44: ...and the fuel is not provided check the feeder according to its manual Fuel feeder not operating does not provide fuel Check if feeder wires are correctly connected to terminals If STB temperature lim...

Page 45: ...45...

Page 46: ...46...

Page 47: ...47...

Page 48: ...48 ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www plum pl National Waste Disposal No 000009381...

Reviews: