temperature  drops  below  the  value  of  the 
parameter: 
Service settings 

 CH and HUW settings 

  CH  pump  activation  temperature  and 

then  for  a  period  of  10  minutes  there  has 
been no growth. 
Cleaning from residual of spent fuel is carried 
out  by  operation  modes  of  moving  grate,  in 
accordance  with  the  set  parameters  in  the 
menu: 
Service  settings 

→ 

Burner  settings 

→ 

Cleaning 

8.12

 

HUW settings 

The  controller  regulates  temperature  of  the 
HUW 

container, 

providing 

that 

the 

temperature  sensor  is  connected.  When  the 
HUW  temperature  sensor  is  disconnected  – 
the  information  about  it  is  displayed  in  the 
main window.  
By  setting:  HUW  settings 

    HUW  pump 

mode user is able to: 

 

deactivate  feeding  the  HUW  container, 
parameter Off

 

setting  HUW  priority,  by  parameter 
Priority – then CH pump is deactivated to 
feed the HUW container quicker, 

 

set  simultaneous  operation  of  CH  and 
HUW  pump  with  the  parameter  No 
priority

8.13

 

HUW preset temperature setting 

Preset  temperature  HUW  is  defined  by 
parameter: 
HUW 

settings 

 

HUW 

preset 

temperature 

8.14

 

Hysteresis of HUW container 

Below temperature HUW preset temp. minus 
HUW  hysteresis  the  HUW  pump  will  activate 
to feed the HUW container. 

 

By  small  hysteresis  value  HUW 
pump will activate faster after HUW 
temperature decrease. 

8.15

 

Activation of the SUMMER 

function 

To  activate  SUMMER  function  which  allows 
feeding  the  silo  during  summer,  without 
necessity  to  activate  CH  installation  and 
mixers  periods,  it  is  required  to  set  the 

menu: Summer/Winter 

→ 

SUMMER mode 

for Summer. 

 

Attention:  when  boiler  operates 
without  heating  buffer  and  the 
controller 

is 

switched 

into 

SUMMER  mode,  than  Standard 
mode 

operation 

is  

recommended. 

 

It  is  not  allowed  to  activate 
function summer when HW pump 
is disconnected or damaged. 

Function 

SUMMER 

can 

be 

activated 

automatically,  on  the  basis  of  readings  from 
weather sensor. Use following parameters to 
activate this function: 
Summer/Winter 

→ 

SUMMER  mode

  → 

Auto 
If  the  automatic  detection  of  summer  mode 
is  switched  on,  you  can  set  the  parameters: 
SUMMER mode act. temperature, so outdoor 
temp. above which the summer mode will be 
switched  on  and  SUMMER  mode  deact. 
temperature
,  so  outdoor  temp.  below  which 
the SUMMER mode will be switched off). 

8.16

 

HUW container disinfection 

The controller can automatically, periodically 
make HUW container warm up to 70ºC. It is 
done  to  remove  bacterial  flora.  Function  is 
activated in the menu: 
HUW settings 

→ 

HUW disinfection 

 

It  is  absolutely  important  to  inform 
all the inmates about activating the 
disinfection  function.  There  is  a 
danger of scalding with hot water. 

Once  a  week  at  night,  in  Monday  at  2  a.m. 
the controller increases temperature of HUW 
container.  After  10  minutes  of  keeping  the 
silo  at  70ºC  the  HUW  pump  is  deactivated 
and  the  silo  returns  to  its  normal  operation. 
It  is  not  advisable  to  activate  disinfection 
function  while  the  service  of  HUW  is 
deactivated. 

8.17

 

 Mixer circuit settings 

Settings of first mixer circle are in the menu: 
Mixer 1 settings 
Settings  for  other  mixers,  after  connecting 
additional  module  B  and  C  are  in  the 
following  positions  of  the  menu  and  are 
identical for each circuit. 

Summary of Contents for ecoMAX920P1-S TOUCH

Page 1: ...TALLATION AND OPERATING MANUAL ISSUE 1 0_EN Functions available in additional module B ecoSTER TOUCH ecoNET300 ecoNET apk ecoNET app www econet24 com Devices are not standard equipment of the controll...

Page 2: ...eam condensation conditions and cannot be exposed to water MAIN PRINCIPLES OF PROPER BOILER OPERATION WITH INDIVIDUAL FUZZY LOGIC The controller must be programmed individually for a given boiler and...

Page 3: ...ROTECTION LEVEL 24 12 5 ELECTRIC CONNECTION 24 12 6 ELECTRIC SCHEME 26 12 7 CONNECTION OF TEMPERATURE SENSORS 28 12 8 CONNECTING THE WEATHER TEMP SENSOR 28 12 9 CONNECTING THE EXHAUST TEMPERATURE SENS...

Page 4: ...is intended for boiler manufacturers Before applying the controller a boiler manufacturer should check if the controller s matching with the given boiler type is proper and whether it can cause dange...

Page 5: ...bserve these instructions 4 Storage of documentation This assembly and operation manual as well as any other applicable documentation should be stored diligently so that it was available at any time I...

Page 6: ...6...

Page 7: ...USER SETTINGS ecoMAX920P1 S TOUCH...

Page 8: ...n Decrease value Schedule Night time circ pump decrease Summer Winter SUMMER mode Summer Winter Auto SUMMER mode activation temp SUMMER mode deactivation temp Mixer 1 5 settings 5 Preset mixer tempera...

Page 9: ...10 Functions affecting preset boiler temperature Following symbols signal respectively room thermostat contacts open preset room temperature reached preset boiler temperature decrease due to activated...

Page 10: ...er e g boiler inactivity period in STOP mode Fan is switched on with the power set by Firing up airflow parameter Small fuel dosage is given 20 of basic dosage If during period set by Ignition test ti...

Page 11: ...teresis H2 and 30 H1 hysteresis Hysteresis H1 and H2 of power modulation Operation in Fuzzy Logic mode In Fuzzy Logic mode the controller automatically regulates burner power to allow boiler operation...

Page 12: ...ng the fuel and performs cyclic blowing according to Blowing time and Blowing pause settings in order to burn the remaining fuel After flame brightness dropping below Burning out end threshold value i...

Page 13: ...the menu Summer Winter SUMMER mode for Summer Attention when boiler operates without heating buffer and the controller is switched into SUMMER mode than Standard mode operation is recommended It is no...

Page 14: ...m temperature 18 C the controller will move heating curve by 2 C In some cases described in point 8 18 it can be necessary to adjust heating curve shift In this configuration room thermostat is able t...

Page 15: ...oiler Time periods allow setting temperature reduction in given time period i e at night or when user leaves the heated room Thanks to it preset temperature can be reduced automatically without loss o...

Page 16: ...Fuel level 0 There is a possibility to skip the calibration process if the parameters are set correctly Feeder efficiency and Capacity of tank which are in Service settings Burner settings Operation 8...

Page 17: ...er operation status alarms allows to set controller parameters and its operation modes it also serves as an additional panel controlling the boiler 8 26 Cooperation with internet module The controller...

Page 18: ...18...

Page 19: ...19 INSTALLATION AND SERVICE SETTINGS ecoMAX920P1 S TOUCH...

Page 20: ...c If the return sensor is clip on insulate it thermally from the surroundings and improve thermal contact with the pipe by using thermal grease Boiler s preset temperature must be set high enough to p...

Page 21: ...te 80 C Boiler settings Minimum boiler temperature 75 C Service settings Boiler settings CH pump activation temperature 55 C Service settings CH and HUW settings Buffer support Yes Service settings Bu...

Page 22: ...gs Buffer settings Buffer loading start temperature 50 C Service settings Buffer settings Buffer loading end temperature 75 C Service settings Buffer settings Mixer 1 2 3 4 support CH on Service setti...

Page 23: ...ontroller 5 IP20 from the front side of the executive module IP00 from the side of the executive module cover against damage to the STB capillary placed in the terminal box 12 Controller installation...

Page 24: ...ction device RCD with inrush current I n 30 mA protecting against the effects of the regulator including protection against fire After deactivating the controller there still can be a dangerous voltag...

Page 25: ...from the casing of the controller as shown below Cables secured from splitting should be connected to screw terminals of the 6 connector Cables should be put through cable outlets in the casing 1 and...

Page 26: ...otor AS ash removal servomotor RT room panel or ISM radio module Lambda probe module B module to support additional heating circuits BT boiler temp sensor type CT4 FS feeder temp sensor type CT4 RS bo...

Page 27: ...rcuit temp sensor type CT4 T3 buffer upper temp sensor type CT4 T4 buffer lower temp sensor type CT4 LS fuel level sensor cooperating with bunker feeder T standard mixer room thermostat H voltage outp...

Page 28: ...between these wires should be 100 mm Do not allow sensor wires to contact hot parts of the boiler and heating system Wires of temperature sensors are heat resistant to the temperature not exceeding 1...

Page 29: ...2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S Pt1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8...

Page 30: ...al module B Exemplary wiring diagram for connecting auxiliary boiler to the controller 1 additional module B 2 auxiliary boiler gas or oil 3 relay RM 84 2012 35 1006 and base GZT80 RELPOL By standard...

Page 31: ...enu Service settings Boiler settings Auxiliary boiler and set zero value for its switching on temperature Exemplary external alarm device connection 1 additional module B 2 external alarm device 3 rel...

Page 32: ...s power indicator of valve opening has been calibrated Attention in mixers 2 3 4 5 the calibration is automatic after switching on the mains power In case of these mixers wait until indicator of valve...

Page 33: ...hich is not the controller s equipment Connect D D wires to G3 socket in the controller Maximum cables length to room panel depends on wires cross section and for 0 25 mm2 wire it should not exceed 30...

Page 34: ...wer increasing Stoker emptying time Cycle Poker operation time Poker pause Stoker emptying time Roto Poker operation time Poker pause Stoker emptying time Cycle x K Poker operation time Poker pause Po...

Page 35: ...ing start temperature Buffer loading end temperature Mixer 1 5 settings Thermostat selection Mixer support OFF CH ON Floor ON Only pump Minimum mixer temperature Maximum mixer temperature Proportional...

Page 36: ...ng the fuel Feeder 2 minimum time Minimum operation time for feeder placed in burner Feeder 2 operation time Determines operation time of additional feeder bunker feeder The feeder is connected to add...

Page 37: ...ted after finishing of which it will start operation again increasing the device s power to preset operation conditions Mechanism 2 when the burner finishes its operation in Burning out Burning off mo...

Page 38: ...lt in excessive CH installation cooling since with such settings CH pump is off CH pump standstill parameter during HUW loading prevents it by enabling periodical CH pump activation during loading of...

Page 39: ...eset temperature the supply of mixer pump will be off After decreasing circuit temperature by 2 C pump is switched on again This option is usually used to control floor heating pump when it cooperates...

Page 40: ...ue to 0 switches alarm off Outputs test time After this time all devices that were switched ON in Manual control menu will be switched off automatically Show advanced Available options YES displays hi...

Page 41: ...lame striking back will be off in this case Protective function against flame strike back does not work when feeder sensor is disconnected or when it s damaged or when the controller is not supplied T...

Page 42: ...the form of two files file with panel program and a file with program for module A of the controller Place new firmware directly on the memory card do not place data in a folder Then connected electri...

Page 43: ...necessary information read from nameplates In case of the controller it is essential to know its serial number If the serial number is unknown provide its model design and year of production Controlle...

Page 44: ...and the fuel is not provided check the feeder according to its manual Fuel feeder not operating does not provide fuel Check if feeder wires are correctly connected to terminals If STB temperature lim...

Page 45: ...45...

Page 46: ...46...

Page 47: ...47...

Page 48: ...48 ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www plum pl National Waste Disposal No 000009381...

Reviews: