14.3

 

 BUFFER SERVICE SETTINGS 

Buffer settings 

 

Activating operation 

Parameter serves to activating buffer operating mode. Available after 
connecting additional module B and buffer temperature sensors. 

Loading start temperature 

Parameter buffer loading start temperaturę defines high temperaturę 
below  which  buffer  feeding  starts.  Buffer  feeding  proces  is  finished 
when  low  temperaturę  reaches  value  defined  in  parameter  buffer 
feeding end temperature.   

Loading end temp. 

14.4

 

 MIXER SERVICE SETTINGS 

Mixer settings 1,2,3,4,5 

Mixer support 

 

  Off 

Mixer serwomotor and pump are not active 

  CH on 

Applicable  when  mixer  cycle  powers  heating  installation  of  CH. 
Maximum  temperaturę  of  mixer  cycle  is  not  limited,  mixer  is  fully 
opened during alarms i.e. boiler overheating. Attention: do not activate 
this  option  when  installation  is  made  of  pipes  sensitive  to  high 
temperature. In such situations it is recommended to set mixer service 
on FLOOR 

  Floor on 

Is used when mixer cycle powers floor installation. Maximum power of 
mixer cycle is limited to value of parameter max preset mixer 
temperature. 
Attention: After choosing option FLOOR, it is necessary to set 
parameter max mixer preset temperature on such a value to not 
damage the floor and avoid scalding risk. 

Boiler Increase byHUW and Mixer 

Parameter determines how high the boiler temperature will be increased 
to  load  HW  silo,  buffer  and  mixer  cycle.  Temperature  increase  is  only 
realizing  when  it  is  necessary.  When  preset  boiler  temperature  is  at 
sufficient level then controller will not change it due to the fact of feeding 
the  HW silo,  buffer or  mixer  cycle.  Increasing  preset  boiler  temperature 
during  feeding  HW  silo  is  signaled  with  letter  “C”  in  main  window  of 
displayer 

HUW operation extension* 

Available  after  connecting  HW  sensor.  After  feeding  HW  silo  and 
deactivating HW pump may be a risk of boiler overheating. It happens in 
case  when  preset  HW  temperature  was  higher  than  boiler  preset 
temperature. This issue is exceptionally important in HW pump operation 
in SUMMER mode, when pump is deactivated. To cool off the boiler HW 
pump operation can be prolonged by 

HW operation time prolongation

.

 

Circulation standstill time 

Parameters available after connecting additional module MX.03. Pausing 
time between periods of circulation pump operation is defined with value 
of  parameter 

Circulation  stop  time

 

(recommended  setting  15-40  min.) 

Circular  pump  operates  constantly  during 

circulation  operation  time

(recommended setting 60-120s) 

Circulation operation time 

Exchanger* 

Parameter available after activating option  Show advanced setup = 
YES.  It  only  refers  to  hydraulic  installation  with  heat  exchanger 
between open and closed circuit, point 12.2. Available options: 

 

YES  (boiler  pump  operates  constantly  in  short  circuit  boiler 

– 

exchanger,  it  is  not  excluded  i.e.  from  SUMMER  function  or  HW 
priority) 

 

NO (pump operates normally) 

Summary of Contents for ecoMAX850P1-V

Page 1: ...ns available in additional module B functions available in additional module C MX 03 room panel ecoSTER200 non standard option USER MANUAL FOR MAINTENANCE AND INSTALLATION EDITION 1 1 APPLIES FOR HARD...

Page 2: ...DITIONS 23 12 2 INSTALLATION REQUIREMENTS 23 12 3 INSTALLATION 24 12 4 ELECTRIC CIRCUIT CONNECTION 24 12 5 SAFETY CONNECTIONS 26 12 6 ELECTRIC SCHEME 26 12 7 TEMPERATURE SENSORS CONNECTION 27 12 8 WEA...

Page 3: ...the feeder etc The controller is for boiler producers The boiler producer before its use should check if the cooperation between the controller and the boiler is correct and is not dangerous The contr...

Page 4: ...r s manual of the controller is divided into two parts for the user and for the installer However in both parts vital information concerning safety is included That is why the user should get aquainte...

Page 5: ...USER MANUAL OF THE CONTROLLER ecoMAX850...

Page 6: ...ature SUMMER Mixer settings 1 2 3 4 5 Preset mixer temperature Mixer room thermostat Weather control mixer Heating curve Mixer Curve shift Room temperatur factor Night time decrease Boiler Mixer 1 Mix...

Page 7: ...temperature decrease due to activated time spans C Boiler preset temperature during loading the hot water boiler HW M Boiler preset temperature increase from mixer circulation P weather control switc...

Page 8: ...etting parameters of its operation MENU button without connecting it to the electrical power After making sure that fuel is in the silo and the hatch is closed the boiler can be switched on 8 4 BOILER...

Page 9: ...ler settings Regulation mode Standard mode operation Boiler output regulation begins when boiler temperature approaches preset temperature i e when the boiler sensor reaches Preset boiler temperature...

Page 10: ...rature of the boiler Operation and pause time of the feeder in SUPERVISION mode is set using following parameters Feeding time SUPERVISION Period time SUPERVISION and Air flush intensity SUPERVISION T...

Page 11: ...following parameters to activate this function Menu HUW settings Auto detection SUMMER Activating temp SUMMER Deactivating temp SUMMER 8 14 HOT WATER FEEDER DISINFECTION The controller can automatical...

Page 12: ...will move heating curve by 2 degrees C In some cases described in point 8 16 it can be necessary to adjust heating curve movement In this configuration room thermostat ecoSTER is able to reduce temper...

Page 13: ...low and in warmer time too high it is recommended to reduce parameter heating curve parallel shift and choose higher heating curve Buildings which are poorly isolated require setting heating curve wi...

Page 14: ...window of the display Pic 12 Signalling time periods 8 18 CIRCULAR PUMP CONTROL Settings are in MENU Night time decrease Circular pump oraz Menu Service settings CH and HUW settings Settings of time...

Page 15: ...el level reaches expected minimum parameter value should be set this way Menu Boiler settings Fuel level Fuel level calibration Fuel level 0 8 20 COOPERATION WITH ADDITIONAL FEEDER After connecting ad...

Page 16: ...cated in the top portion of the controller s main housing Power supply to the fan and feeder will be reactivated Attention Boiler overheating is an abnormal condition therefore the cause must be found...

Page 17: ...19 USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS ecoMAX850P...

Page 18: ...y it is necessary to isolate it thermically from surroundings and improve thermal contact with pipe Preset silo temperature must be set so high to ensure thermal power for mixer cycle when at the same...

Page 19: ...boiler settings Min preset boiler temperature 75 C menu service settings boiler settings CH pump activating temperature 55 C menu service settings CH and HUW settings Activating operation buffer servi...

Page 20: ...e active menu service settings buffer settings Buffer loading start temperature 50 menu service settings buffer settings Buffer loading stop temperature 75 menu service settings buffer settings Mixer...

Page 21: ...rays Temperature of storage and transport should be within scope 15 65 degrees C During transport the controller can not be exposed to vibrations bigger than typical for transport of boilers 12 CONTRO...

Page 22: ...troller on assembly surface where 1 cover 2 base 3 screw for cover 4 plug 5 screw for assembly surface 6 assembly surface 12 4 ELECTRIC CIRCUIT CONNECTION The controller is adapted to current 230V 50H...

Page 23: ...the controller should be led through cable glands Cable glands should be screwed Make sure that glands are correctly screwed by pulling wire Length of isolation of external tire of wires should be mi...

Page 24: ...re sensor CT2S T7 mixer temperature sensor TB connection of mixer room thermostat P controlling panel ecoSTER200 room panel with room thermostat function replacing TB or TM D D connection to additiona...

Page 25: ...ires of the sensors are resistant to temperature not exceeding 100 degrees C 12 8 WEATHER SENSORS CONNECTION The controller cooperates solely with weather sensor type CT4 P The sensor should be instal...

Page 26: ...own on Pic 17 12 12 BOILER ROOM THERMOSTAT CONNECTION Room thermostat for boiler circuit can switch off the burner operation or switch off the CH boiler pump In order to thermostat switch off boiler o...

Page 27: ...ng alarms compatible with alarm signal codes causes activation of additional boiler When pellet boiler is fired up and its temperature exceedes preset value i e 25 degrees C then controller switches o...

Page 28: ...ller 2 external alarm device 3 transmitter Then in order to operate correctly set proper code for active alarms signal in menu Menu Service settings Boiler settings Alarms Choosing value 127 causes ac...

Page 29: ...documentation Do not confuse opening direction with closing direction Connect electrical power to the controller and switch it into STAND BY mode Check if wires for mixer opening and closing are not s...

Page 30: ...which has following functions Room thermostat controls up to 3 thermostats Controlling panel for the boiler Alarm signal Fuel level indicator 4 way connection Connect accordingly to point 12 6 2 way c...

Page 31: ...e Poker p after bur offe Cleaning airflow Supervision Supervision time Feed time Cycle time Blow in output Min airflow output Fuel detection time Max burner temperature Additional feeder operation tim...

Page 32: ...RATION feeder pause time Blow in for Min output kW Blow in output for minimum boiler output 30 Feeder efficiency Feeder fuel efficiency in kg h Energy density Fuel calorific in kWh kg Tank capacity Fu...

Page 33: ...The temperature below which the controller counts down the no fuel detection time Max burner temperature Determines maximum temperature of feeder when there is alarm of exceeding maximum feeder temper...

Page 34: ...when HW l Available after connecting HW sensor Prolonged feeding of HW silo during priority HW deactivated may cause to overcooling of the CH installation because CH pump is deactivated Parameter CH p...

Page 35: ...e will be increased to load HW silo buffer and mixer cycle Temperature increase is only realizing when it is necessary When preset boiler temperature is at sufficient level then controller will not ch...

Page 36: ...ature Parameter serves two functions allows restricting setting too high mixer preset temperatur Automatic control also will not cause exceeding preset temperature above value set in this parameter wi...

Page 37: ...MP EXCEEDING This alarm occurs when the contact opens the feeder sensor The alarm is reset by turning the regulator The controller can not be used as sole protection of boiler against back fire Additi...

Page 38: ...not protect the installation against freezing 17 3 PUMP ANTI STANDSTILL FUNCTION The controller does the function of CH HW and Mixer pumps protection against getting stale 17 4 NETWORK FUSE REPLACEMEN...

Page 39: ...r in fumes It is not recommended to change these parameters if regulation time and stability of keeping preset amount of air on required level Periodical calibration of Lambda sond readings can be nec...

Page 40: ...ition it should be unlocked by untwisting the cover and twisting the button according to documentation of boiler producer Check the fan and replace it if necessary 5 Additional ffeder is not working m...

Page 41: ...rners should be consultet with Company Plum Sp z o o In order to load new parameters go to Menu service settings special password and choose proper boiler burner Default settings can also be loaded by...

Page 42: ...48 7 7 964 556 4411 7 905 579 6633 8 963 695 44 11 E mail 5564411 mail ru 5564411 ooo bioterm ru...

Reviews: