Plum ecoMAX850P1-V Manual Download Page 12

14 

 

When  this  value  is  reduced  correctly  then 
room temperature increase will be stopped.  
 

Mixer with weather sensor setting 

(without  room  panel  ecoSTER200)  Set 
parameter 

mixer  weather  control

 

in  position 

on.  Adjust  weather  curve  according  to  point 
8.16 
 
Using parameter 

paralel curve movement

 

set 

required  room  temperature  according  to 
formula: 
Required  room  temperature  =  20°C  + 
heating curve paralel movement.  

Example.

 

To  reach  room  temperature  25°C  value  of 
heating  curve  movement  must  be  set  for 
5°C. To reach room temperature 18°C value 
of  heating  curve  paralel  movement  must  be 
set for -2°C. 
 
In  this  configuration  a  thermostat  can  be 
connected. It will level inaccuracy of heating 
curve adjustement in case when its value will 
be too big. In such case value of decrease of 
preset  mixer  room  temperature  from 
thermostat  should  be  set  i.e.  for  2°C

.

After 

discontecting  thermostat  plugs  preset  mixer 
cycle temperature will be reduced. By correct 
adjustement  of  this  reduction  will  stop 
temperature  increase  of  temperature  in 
heated room. 
 

Mixer  with  weather  sensor  and  room 
panel ecoSTER200 settings  

Set  parameter 

Mixer  weather  control

.  In 

position off. 
 
Adjust weather curve according to point 8.16 
 
Controller  ecoSTER200  automatically  moves 
the heating curve depending on preset room 
temperature. 

The 

controller 

relates 

adjustements to 20 degrees C, i.e. for preset 
room  temperature  =  22  degrees  C  the 
controller  will  move  heating  curve  by  2 
degrees C, for preset room temperature = 18 
degrees  C  the  controller  will  move  heating 
curve  by  -2  degrees  C.  In  some  cases 
described in point 8.16 it can be necessary to 
adjust heating curve movement. 

 
In  this  configuration  room  thermostat 
ecoSTER is able to: 
reduce  temperature  of  heating  cycle  by  a 
constant  value,  when  preset  temperature  in 
a  room  will  be  reached.  Similarly like  it  was 
described 

in 

previous 

point 

(not 

recommended), or  
automatically,  constantly  correct  heating 
cycle temperature.   
It  is  not  recommended  to  use  both  these 
possibilities at the same time.  
 
Automatic correction of room temperaturę is 
done according to formula: 
 
Correction  =  (preset  room  temperature  – 
measured  room  temperature)  x  room 
temperature factor / 10 
 
Example.  
Preset  temperature  in  heating  room  (set  in 
ecoSTER200)  =  22  degrees  C.  Measured 
temperature  in  room  (using  ecoSTER200)  = 
20 degrees C. 

room temperature factor

 = 15 

Preset  mixer  temperature  will  be  increased 
by (22 degrees C – 20 degrees C) x 15/10 = 
3  degrees  C.  Correct  value  of  parameter 
must  be  found  room  temperature  factor. 
Scope: 0…50. The bigger value of factor the 
bigger 

correction 

of 

preset 

boiler 

temperature  factor.  When  set  on  value  “0” 
preset  mixer  temperature  is  not  corrected. 
Attention:  setting  too  high  value  of  room 
temperature  factor  may  cause  cyclic  room 
temperature fluctuations.  

8.16

 

WEATHER CONTROL 

Depending 

on 

measured 

outside 

temperature, automatically controlled can be 
either  preset  boiler  temperature  and  mixer 
cycles  temperatures.  By  correct  adjustment 
of  heating  curve  temperature  of  heating 
circuits  is  counted  automatically  depending 
on value of external temperature.  Thanks to 
that  by  choosing  proper  heating  curve  for 
given  building,  room  temperature  remains 
approximately  the  same  –  no  matter  what 
outside temperature.  

 

Summary of Contents for ecoMAX850P1-V

Page 1: ...ns available in additional module B functions available in additional module C MX 03 room panel ecoSTER200 non standard option USER MANUAL FOR MAINTENANCE AND INSTALLATION EDITION 1 1 APPLIES FOR HARD...

Page 2: ...DITIONS 23 12 2 INSTALLATION REQUIREMENTS 23 12 3 INSTALLATION 24 12 4 ELECTRIC CIRCUIT CONNECTION 24 12 5 SAFETY CONNECTIONS 26 12 6 ELECTRIC SCHEME 26 12 7 TEMPERATURE SENSORS CONNECTION 27 12 8 WEA...

Page 3: ...the feeder etc The controller is for boiler producers The boiler producer before its use should check if the cooperation between the controller and the boiler is correct and is not dangerous The contr...

Page 4: ...r s manual of the controller is divided into two parts for the user and for the installer However in both parts vital information concerning safety is included That is why the user should get aquainte...

Page 5: ...USER MANUAL OF THE CONTROLLER ecoMAX850...

Page 6: ...ature SUMMER Mixer settings 1 2 3 4 5 Preset mixer temperature Mixer room thermostat Weather control mixer Heating curve Mixer Curve shift Room temperatur factor Night time decrease Boiler Mixer 1 Mix...

Page 7: ...temperature decrease due to activated time spans C Boiler preset temperature during loading the hot water boiler HW M Boiler preset temperature increase from mixer circulation P weather control switc...

Page 8: ...etting parameters of its operation MENU button without connecting it to the electrical power After making sure that fuel is in the silo and the hatch is closed the boiler can be switched on 8 4 BOILER...

Page 9: ...ler settings Regulation mode Standard mode operation Boiler output regulation begins when boiler temperature approaches preset temperature i e when the boiler sensor reaches Preset boiler temperature...

Page 10: ...rature of the boiler Operation and pause time of the feeder in SUPERVISION mode is set using following parameters Feeding time SUPERVISION Period time SUPERVISION and Air flush intensity SUPERVISION T...

Page 11: ...following parameters to activate this function Menu HUW settings Auto detection SUMMER Activating temp SUMMER Deactivating temp SUMMER 8 14 HOT WATER FEEDER DISINFECTION The controller can automatical...

Page 12: ...will move heating curve by 2 degrees C In some cases described in point 8 16 it can be necessary to adjust heating curve movement In this configuration room thermostat ecoSTER is able to reduce temper...

Page 13: ...low and in warmer time too high it is recommended to reduce parameter heating curve parallel shift and choose higher heating curve Buildings which are poorly isolated require setting heating curve wi...

Page 14: ...window of the display Pic 12 Signalling time periods 8 18 CIRCULAR PUMP CONTROL Settings are in MENU Night time decrease Circular pump oraz Menu Service settings CH and HUW settings Settings of time...

Page 15: ...el level reaches expected minimum parameter value should be set this way Menu Boiler settings Fuel level Fuel level calibration Fuel level 0 8 20 COOPERATION WITH ADDITIONAL FEEDER After connecting ad...

Page 16: ...cated in the top portion of the controller s main housing Power supply to the fan and feeder will be reactivated Attention Boiler overheating is an abnormal condition therefore the cause must be found...

Page 17: ...19 USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS ecoMAX850P...

Page 18: ...y it is necessary to isolate it thermically from surroundings and improve thermal contact with pipe Preset silo temperature must be set so high to ensure thermal power for mixer cycle when at the same...

Page 19: ...boiler settings Min preset boiler temperature 75 C menu service settings boiler settings CH pump activating temperature 55 C menu service settings CH and HUW settings Activating operation buffer servi...

Page 20: ...e active menu service settings buffer settings Buffer loading start temperature 50 menu service settings buffer settings Buffer loading stop temperature 75 menu service settings buffer settings Mixer...

Page 21: ...rays Temperature of storage and transport should be within scope 15 65 degrees C During transport the controller can not be exposed to vibrations bigger than typical for transport of boilers 12 CONTRO...

Page 22: ...troller on assembly surface where 1 cover 2 base 3 screw for cover 4 plug 5 screw for assembly surface 6 assembly surface 12 4 ELECTRIC CIRCUIT CONNECTION The controller is adapted to current 230V 50H...

Page 23: ...the controller should be led through cable glands Cable glands should be screwed Make sure that glands are correctly screwed by pulling wire Length of isolation of external tire of wires should be mi...

Page 24: ...re sensor CT2S T7 mixer temperature sensor TB connection of mixer room thermostat P controlling panel ecoSTER200 room panel with room thermostat function replacing TB or TM D D connection to additiona...

Page 25: ...ires of the sensors are resistant to temperature not exceeding 100 degrees C 12 8 WEATHER SENSORS CONNECTION The controller cooperates solely with weather sensor type CT4 P The sensor should be instal...

Page 26: ...own on Pic 17 12 12 BOILER ROOM THERMOSTAT CONNECTION Room thermostat for boiler circuit can switch off the burner operation or switch off the CH boiler pump In order to thermostat switch off boiler o...

Page 27: ...ng alarms compatible with alarm signal codes causes activation of additional boiler When pellet boiler is fired up and its temperature exceedes preset value i e 25 degrees C then controller switches o...

Page 28: ...ller 2 external alarm device 3 transmitter Then in order to operate correctly set proper code for active alarms signal in menu Menu Service settings Boiler settings Alarms Choosing value 127 causes ac...

Page 29: ...documentation Do not confuse opening direction with closing direction Connect electrical power to the controller and switch it into STAND BY mode Check if wires for mixer opening and closing are not s...

Page 30: ...which has following functions Room thermostat controls up to 3 thermostats Controlling panel for the boiler Alarm signal Fuel level indicator 4 way connection Connect accordingly to point 12 6 2 way c...

Page 31: ...e Poker p after bur offe Cleaning airflow Supervision Supervision time Feed time Cycle time Blow in output Min airflow output Fuel detection time Max burner temperature Additional feeder operation tim...

Page 32: ...RATION feeder pause time Blow in for Min output kW Blow in output for minimum boiler output 30 Feeder efficiency Feeder fuel efficiency in kg h Energy density Fuel calorific in kWh kg Tank capacity Fu...

Page 33: ...The temperature below which the controller counts down the no fuel detection time Max burner temperature Determines maximum temperature of feeder when there is alarm of exceeding maximum feeder temper...

Page 34: ...when HW l Available after connecting HW sensor Prolonged feeding of HW silo during priority HW deactivated may cause to overcooling of the CH installation because CH pump is deactivated Parameter CH p...

Page 35: ...e will be increased to load HW silo buffer and mixer cycle Temperature increase is only realizing when it is necessary When preset boiler temperature is at sufficient level then controller will not ch...

Page 36: ...ature Parameter serves two functions allows restricting setting too high mixer preset temperatur Automatic control also will not cause exceeding preset temperature above value set in this parameter wi...

Page 37: ...MP EXCEEDING This alarm occurs when the contact opens the feeder sensor The alarm is reset by turning the regulator The controller can not be used as sole protection of boiler against back fire Additi...

Page 38: ...not protect the installation against freezing 17 3 PUMP ANTI STANDSTILL FUNCTION The controller does the function of CH HW and Mixer pumps protection against getting stale 17 4 NETWORK FUSE REPLACEMEN...

Page 39: ...r in fumes It is not recommended to change these parameters if regulation time and stability of keeping preset amount of air on required level Periodical calibration of Lambda sond readings can be nec...

Page 40: ...ition it should be unlocked by untwisting the cover and twisting the button according to documentation of boiler producer Check the fan and replace it if necessary 5 Additional ffeder is not working m...

Page 41: ...rners should be consultet with Company Plum Sp z o o In order to load new parameters go to Menu service settings special password and choose proper boiler burner Default settings can also be loaded by...

Page 42: ...48 7 7 964 556 4411 7 905 579 6633 8 963 695 44 11 E mail 5564411 mail ru 5564411 ooo bioterm ru...

Reviews: