Pic. 10 Time periods edition.
Below sample preset night temperature
reduction is presented.
Attention, defining time periods
during one day must be started at
00:00!
Pic. 11 Sample of defining time periods.
In this example from 00:00 to 06:00 the
controller will set preset silo temperature by
3 degrees C. Since 06:00 to 09:00 the
controller leaves preset silo temperature at
preset level (without reductions).Since 22:00
to 23:59 the controller will reduce preset silo
temperature by 3 degrees C.
Time period is omitted by setting
period reduction for value “0” even
if scope of hours is set in it
Reduction of preset silo temperature
from time period is signalled with
the letter „S” in main window of the
display.
Pic. 12 Signalling time periods.
8.18
CIRCULAR PUMP CONTROL
Settings are in:
MENU
→
Night time decrease
→
Circular
pump.
oraz
Menu
→
Service settings
→
CH and HUW
settings
Settings of time control of circular pump are
analogical to settings of night reductions. In
defined time periods circular pump is
deactivated. In omitted periods the circular
pump is switched into position
Circular
operation time
every
Circular halt time
.
8.19
FUEL LEVEL CONFIGURATION
Fuel level indicator activating
To activate displaying fuel level following
parameters are to be set
Menu – Boiler setting – Fuel level –
alarm level
On value bigger than “0”, i.e. 10%
Twisting “TOUCH and PLAY” knob in main
window fuel level is displayed in main
window.
Tip: fuel level can also be seen in room panel
ecoSTER200 (room panel is not a standard
option of the controller).
Pic. 13 Auxiliary window with fuel level display.