2.

 

GENERAL INFORMATION 

The  controller  is  a  modern  electronic  device 
designed  to  handling  the  work  of  the  pellet 
boiler  using  help  of  optical  flame  brightness 
sensor.  The  device  is  compactly  build,  easy 
to install. 
It can control the work of central heating and 
hot  water  circuits  and  also  control  the  work 
of  5  mixing    heating  circuits.  The  required 
temperature of heating circuits can be set on 
the  basis  of  data  obtained  from  the  main 
sensor.  The  possibility  of  cooperation  with 
room thermostats, separate for each heating 
circuit 

is 

beneficial 

for 

maintaining 

comfortable  temperature  in  heating  rooms. 
Moreover,  the  device  turns  on  the  spare 
boiler (gas or oil one) 
The  controller  can  cooperate  with  additional 
steering  panel  located  in  living  rooms  and 
additional modul of lambda λ sensor.  
Handling  of  the  controller  is  easy  and 
intuitive.  The  controller  can  be  used  within 
the  household  and  in  small  industrial 
buildings. 

3.

 

DATA 

REFERRING 

TO 

DOCUMENTATION 

The  user’s  manual  of  the  controller  is  a 
complementation of boiler documentation. In 
particular  it  is  necessary  to  apply  the  boiler 
documentation.  The  user’s  manual  of  the 
controller  is  divided  into  two  parts:  for  the 
user  and  for  the  installer.  However  in  both 
parts  vital  information  concerning  safety  is 
included.  That  is  why  the  user  should  get 
aquainted  with  both  parts  of  the  user’s 
manual. 

We  do  not  take  responsibility  for  damages 
caused  by  failing  to  observe  the  following 
user manual.  

4.

 

DOCUMENTATION STORAGE 

We  advise  you  to  keep  carefully  this  user 
manual  of  installation  and  maintenance  and 
all other valid documentation,  for immediate 
use  when  needed.  In  case  of  removal  or 
selling  the  device  all  the  documentation 
should be handed to new user or owner.  

5.

 

SYMBOLS AND MARKINGS USED 

Following graphic symbols and markings are 
used in the user manual:

 

-for relevant information and tips, 
 
 -for  vital  information  related  with 
issues of property damage, health and 
life  risk  of  humans  or  domestic 

animals, 

Attention: by these symbols vital information is marked. 
It  is  to  allow  easy  understanding  of  the  user  manual. 
User  and  installer  is  however  required  to  observe 
recommendations not expressed by graphic symbols! 

6.

 

WEEE 2002/96/EG  

 

 

The  packaging  and  product  is  to  be 

utilised  at  the  end  of  using  period  by 
a proper recycling company. 

 

The  product  can  not  be  disposed 

together with ordinary wastes. 

 

The product can not be burned.  

 

Summary of Contents for ecoMAX850P1-R

Page 1: ...ns available in additional module B functions available in additional module C MX 03 room panel ecoSTER200 non standard option USER MANUAL FOR MAINTENANCE AND INSTALLATION EDITION 1 0 APPLIES FOR HARD...

Page 2: ......

Page 3: ...TALLATION REQUIREMENTS 23 12 3 INSTALLATION 24 12 4 ELECTRIC CIRCUIT CONNECTION 24 12 5 SAFETY CONNECTIONS 26 12 6 ELECTRIC SCHEME 26 12 7 TEMPERATURE SENSORS CONNECTION 28 12 8 WEATHER SENSORS CONNEC...

Page 4: ......

Page 5: ...the feeder etc The controller is for boiler producers The boiler producer before its use should check if the cooperation between the controller and the boiler is correct and is not dangerous The cont...

Page 6: ...entation The user s manual of the controller is divided into two parts for the user and for the installer However in both parts vital information concerning safety is included That is why the user sho...

Page 7: ...USER MANUAL OF THE CONTROLLER ecoMAX850P1 R...

Page 8: ...MER Deactv temperature SUMMER Mixer settings 1 2 3 4 5 Preset mixer temperature Mixer room thermostat Weather control mixer Heating curve Mixer Curve shift Room temperatur factor Night time decrease B...

Page 9: ...re decrease due to activated time spans C Boiler preset temperature during loading the hot water boiler HW M Boiler preset temperature increase from mixer circulation P weather control switch on for b...

Page 10: ...ing sure that fuel is in the silo and the hatch is closed the boiler can be switched on 8 4 BOILER TEMPERATURE SETTING The preset boiler temperature and preset circuits temperature can be set in the m...

Page 11: ...reset temperature i e when the boiler sensor reaches Preset boiler temperature Max Min hysteresis Pic 6 Output modulation STANDARD mode where Tzk preset boiler temperature H Max Min Max Min hysteresis...

Page 12: ...ause boiler overheating Maximum time of boiler s operating in supervision mode is defined in parameter Supervision time If after this time in Supervision mode there is no need to restart the boiler bo...

Page 13: ...periodically make HW silo warm up to 70 degrees C It is done to remove bacterial flora It is absolutely important to inform all the inmates about activating the disinfection function There is a dange...

Page 14: ...be necessary to adjust heating curve movement In this configuration room thermostat ecoSTER is able to reduce temperature of heating cycle by a constant value when preset temperature in a room will be...

Page 15: ...e parallel shift and choose higher heating curve Buildings which are poorly isolated require setting heating curve with higher values and for better isolated buildings heating curve will have lower va...

Page 16: ...indow of the display Pic 11 Signalling time periods 8 18 CIRCULAR PUMP CONTROL Settings are in MENU Night time decrease Circular pump and Menu Service settings CH and HUW settings Settings of time con...

Page 17: ...el level reaches expected minimum parameter value should be set this way Menu Boiler settings Fuel level Fuel level calibration Fuel level 0 8 20 COOPERATION WITH ADDITIONAL FEEDER After connecting ad...

Page 18: ......

Page 19: ...19 USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS ecoMAX850P1 R...

Page 20: ...t is necessary to isolate it thermically from surroundings and improve thermal contact with pipe Preset silo temperature must be set so high to ensure thermal power for mixer cycle when at the same ti...

Page 21: ...boiler settings Min preset boiler temperature 75 C menu service settings boiler settings CH pump activating temperature 55 C menu service settings CH and HUW settings Activating operation buffer servi...

Page 22: ...active menu service settings buffer settings Buffer loading start temperature 50 menu service settings buffer settings Buffer loading stop temperature 75 menu service settings buffer settings Mixer se...

Page 23: ...rays Temperature of storage and transport should be within scope 15 65 degrees C During transport the controller can not be exposed to vibrations bigger than typical for transport of boilers 12 CONTRO...

Page 24: ...rface 12 4 ELECTRIC CIRCUIT CONNECTION The controller is adapted to current 230V 50Hz Features of installation 3 way with protecting wire made according with valid law Attention After deactivating the...

Page 25: ...tly screwed by pulling wire Length of isolation of external tire of wires should be minimal maximum 60mm If it is necessary to longer isolate the wire tire they should be connected with each other or...

Page 26: ...al operation of the boiler T7 mixer temperature sensor FS fuel level sensor CS hatch opening sensor P controlling panel ecoSTER200 room panel with room thermostat function replacing TB or TM D D conne...

Page 27: ...ve 2 or 4 CT4 T2 temperature sensor for mixing valve 3 or 5 CT4 T3 upper buffer temperature sensor T4 lower buffer sensor CT4 T room thermostat B extension module C extension module 230V power cord PM...

Page 28: ...res of the sensors are resistant to temperature not exceeding 100 degrees C 12 8 WEATHER SENSORS CONNECTION The controller cooperates solely with weather sensor type CT4 P The sensor should be install...

Page 29: ...own on Pic 16 12 12 BOILER ROOM THERMOSTAT CONNECTION Room thermostat for boiler circuit can switch off the burner operation or switch off the CH boiler pump In order to thermostat switch off boiler o...

Page 30: ...alarms compatible with alarm signal codes causes activation of additional boiler When pellet boiler is fired up and its temperature exceedes preset value i e 25 degrees C then controller switches off...

Page 31: ...where 1 controller 2 external alarm device 3 transmitter Then in order to operate correctly set proper code for active alarms signal in menu Menu Service settings Boiler settings Alarms Choosing valu...

Page 32: ...cumentation Do not confuse opening direction with closing direction Connect electrical power to the controller and switch it into STAND BY mode Check if wires for mixer opening and closing are not swa...

Page 33: ...which has following functions Room thermostat controls up to 3 thermostats Controlling panel for the boiler Alarm signal Fuel level indicator 4 way connection Connect accordingly to point 12 6 2 way c...

Page 34: ...eed time Cycle time Blow in output Delay Min airflow output Fuel detection time Additional feeder operation time Clamps 28 29 delay Boiler settings Thermostat selection Min boiler temperature Max Boil...

Page 35: ...ime Blow in for Min output kW Blow in output for minimum boiler output 30 Feeder efficiency Feeder fuel efficiency in kg h Energy density Fuel calorific in kWh kg Tank capacity Fuel silo capacity for...

Page 36: ...n Options to choose from Deactivated deactivates room thermostat influence on boiler operation Universal activates room thermostat for boiler ecoSTER200 T1 option available after connecting room panel...

Page 37: ...r in the silo can heat up to dangerous temperature It is necessary to use additional protection in the form of thermostatic valves Boiler Increase byHUW and Mixer Parameter determines how high the boi...

Page 38: ...is option is normally used to control floor heating pump in situation when it cooperates with thermostatic valve without servomotor By such action is not recommended It is recommended to use standard...

Page 39: ...u Setting parameter determining value of temperature dead zone for mixer controlling circuit The controller regulates mixer in such a way to keep the temperature of mixer cycle equal to preset value H...

Page 40: ...t pipe is not beneficial because it may cause delay in detecting boiler overheating state Pic 26 Alarm of boiler overheating view 15 2 BOILER TEMP SENSOR FAILURE Alarm appears by boiler sensor damage...

Page 41: ...not protect the installation against freezing 16 3 PUMP ANTI STANDSTILL FUNCTION The controller does the function of CH HW and Mixer pumps protection against getting stale 16 4 NETWORK FUSE REPLACEMEN...

Page 42: ...in fumes It is not recommended to change these parameters if regulation time and stability of keeping preset amount of air on required level Periodical calibration of Lambda sond readings can be nece...

Page 43: ...osition it should be unlocked by untwisting the cover and twisting the button according to documentation of boiler producer Check the fan and replace it if necessary 5 Additional ffeder is not working...

Page 44: ...parameters are those related to Firing up Operation and Burning off The controller is able to change the default settings depending on power and type of the burner Default settings for given boilers...

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ...Ignatki 27a 16 001 Kleosin Poland tel 48 85 749 70 00 fax 48 85 749 70 14 plum plum pl www pum pl www plumelectronics eu...

Reviews: