algorithm of controlling the fan. It should be possibly small to allow the
fan to rotate slowly, without buzzing.
Fuel detection time
Time is measured after decrease in brightness of flame below value
flame detection %
. After deducting this time the controller switches into
firing u
p attempt. After 3 failed attempts, it reports alarm: “failed firing up
attempt.
”
No fuel detection time Tsp
The countdown begins when temperature falls below
No fuel emission
temperature.
After this countdown the controller attempts to fire up the
burner
and after 2 failed attempts activates the “firing up failed” alarm.
No fuel emission temperature
The temperature below which the controller counts down the
no fuel
detection time.
Additional feeder operation
time
Determines additional feeder operation time. Feeder is attached to
additional module B. After this time additional feeder operation is
stopped despite disconnecting joints of fuel level sensor. Joints of fuel
level sensor are located in additional module B.
Cleaning the exchanger
Determines the emission temperature limit above which you will be
prompted to clean the boiler’s heat exchanger.
Clamps 28-29 delay
It is a time delay between starting fuel sensor and automatic entry to the
"PAUSE MODE".
13.2
BOILER SERVICE SETTINGS
Boiler settings
Thermostat selection
Options to choose from:
Deactivated (deactivates room thermostat influence on boiler
operation)
Universal (activates room thermostat for boiler)
ecoSTER200 T1 (option available after connecting room panel
ecoSTER200, boiler operation is dependant on room thermostat
No1 in ecoSTER200)
ecoSTER200 T2 (option available after connecting room panel
ecoSTER200, boiler operation is dependant on room thermostan No
2 in ecoSTER200
– on sensor CT7)
ecoSTER200 T3 (option available after connecting room panel
ecoSTER200, boiler operation is dependant on room thermostat
No3 in ecoSTER200
– on sensor CT7)
Min. boiler timep
Minimum preset boiler temperaturę which can be set in user menu and
minimum temp. which can be set automatically by controller, i.e. from
night reductions etc.
Max. biler time
Maximum
preset boiler temperaturę which can be set in user menu and
minimum temp. which can be set automatically by controller, i.e. from
night reductions etc.
Reserve boiler
Description in point 12.2
Alarms
Description in point 12.3
Boiler cooling temperature
Temperature of boiler cooling off.
Above this temperaturę the controller
activates HW pump and opens mixer cycles to allow boiler cooling off.
The controller activates HW pump if this temperature exceeds maximum
value. The controller will not open mixer cycle when
mixer setting
=
floor
active
Pump off by therm.
Options available
NO (CH boiler pump is not activated when room thermostat starts
operation),
YES (CH boiler pump is deactivated when room thermostat starts
operating)