STOP P.
1.00MPa
Alarm and stop the machine when the air supply
temperature reaches this set value
MAX U.L.
0.80MPa
The Unload Limit Pressure in the Customer Parameter
must be set lower than this value.
RUN TIME
****Hours
The manufacturer can modify the total running time
LOAD TIME
****Hours
The manufacturer can modify the load running time
CLR FAULT
****
Input the history failure password to clear all the
history failures.
CUR UN.BAL.
0006
When (the max. phase current / min. phase current) is
not greater than (1+set value), the unbalance
protection will stop the machine. If the set value is
greater than 15, the unbalance protection will be
unavailable.
LACK PAHSE
005.0
If set
time of phase failure ≥20 seconds, phase failure
doesn’t function; If unbalance protection is activated,
it will stop operation.
DATA
****-**-**
The manufacturer input the product date of the unit.
SERIAL
********
The manufacturer input the product No. of the unit
PHASE PRO.
ON/OFF
ON:Select sequence protection
OFF:Not select sequence protection
POWER FREQ
50H
Set the power frequency
HIGH VOL.
****V
Controller detects the voltage higher than
the set value, the shutdown protection,
reported voltage is too high. Set this value
to 0000, the high voltage function is no
function
LOW VOL.
****V
Controller detects the voltage lower than
the set value, the shutdown protection,
reported voltage is too low. Set this value
to 0000, the low voltage function is no
function
LOW T PRO-
-4
8℃
Controller detects the temperature is lower
than this value, display temperature is
too low, not allowed to start the air
compressor
TIME LIM
0000H
When the compressor run time is greater than TIME
LIM set, the controller will stop the compressor and
alarm ;
If the value set as ‘0000’the function is disable.
ALM STOP
0010H
Warning time over here to set, compressor
report "warning too long" and stop
COM SET PARA
ON/OFF
PARA1
****
9、Calibration parameters
Calibration parameter used to set the controller data
,
Does not allow unauthorized users to view and
modify
PARAMETER
Initial Value
Functions
M
O
T
O
R
TARGET CUR
0000
Enter the current value, the controller will detect
user input value divided by the current to the
current value, calculate the current coefficient
COEF
1.000
Calibration current, the input coefficients.