Rev 6.3.0 12.09.16
PL Reference Manual
18
CHRG
Setting for program number
Parameter
0
1
2
3
GMOD
0
G ON (V)
11.5
GOFF (V)
13.8
GDEL (Min)
10
GEXD (Day)
30
GRUN (Hr)
1.0
LOAD
Setting for program number
Parameter
0
1
2
3
LOFF (V)
11.3
L ON (V)
12.8
LDEL (Min)
10
SET/REG
Setting for program number
Parameter
0
1
2
3
BMAX (V)
15.0
14.2
15.0
14.2
EMAX (V)
16.0
14.0
16.0
14.0
ETIM (Hr)
1.0
0
1.0
0
EFRQ (day)
45
ABSV (V)
14.0
ATIM (Hr)
2.0
FLTV (V)
13.8
HYST (V)
0.4
BRTN (V)
12.3
CHRG (A)
PL20
20
PL40
40
PL60
PL80
60
80
BFRQ (Day)
15
TCMP
0
SET/MODE
Setting for program number
Parameter
0
1
2
3
LSET
1
1
4
4
GSET
2
2
9
9
BSET
0
0
2
2
BAT2 (V)
14.0
PWM
1
ALRM (V)
11.4
SET/EVNT
Setting for program number
Parameter
0
1
2
3
STRT
12
TIME (Hr)
0
STOP
12
TIME (Hr)
25.0
EMOD
2
TMOD
0
7
Settings Used in Programs 0-3
When programs 0-3 are selected, the PL
automatically uses the values below in its
regulation.
The voltage settings are shown correct for 12V
operation. For higher voltages, scale these up
(eg. for a 24V system, multiply each voltage
figure by 2.)
Settings for Program 4
If program 4 is selected, then all menu items can
be accessed.
After TIME, VOLT and PROG, there are entry
points for three further sub menus:
The REG menu allows you to customise the
regulation settings for the PL (see below for
details).
The MODE menu allows you to adjust other
configuration options for the PL.
The EVNT menu allows entry of settings for the
event controller.