User’s Manual of ICS-2x00T Serial Device Server Series
66
4.5.2.10 Modbus Converter Client mode
The ICS Serial devices support standard Modbus protocol and various hardware interfaces (serial and Ethernet). Modbus TCP
and RTU can be used to convert the Modbus protocol. The Modbus master can communicate with the serial network of devices
connected to the serial port of the server converter via a server converter.
The meter receives Modbus TCP / IP data on TCP port 502, translates it to a Modbus RTU, and then forwards it to the
addressed slave device.
Functionally allows monitoring software to access information from slaves for trend analysis, data collection, alarm/event
management, maintenance and other functions. The Modbus Converter Client topology in
Figure 4-5-36
appears.
Figure 4-5-36:
Modbus Converter Client mode Topology
The Modbus Converter Client mode screenshot in
Figure 4-5-37
appears.
Figure 4-5-37:
Modbus Converter Client mode Screenshot
Object
Description
•
TCP Keep-alive
Interval
TCP keep alive interval shows how many seconds the unit waits during an inactive
connection before checking its status. If the unit does not receive a response, it will drop
that connection. The default is 0 minute.
•
Quiescent Time
When the network connection is determined to be idle, the duration of the control
network inactivity will cause the connection to be forced closed.
The default value is 0.