User manual
- DRR245 27
Modbus
Address
Description
Read
Only
Reset
value
0
Device type
RO
EEPROM
1
Software version
RO
EEPROM
5
Slave address
RO
EEPROM
6
Boot version
RO
EEPROM
50
Automatic addressing
WO
-
51
System code comparison
WO
-
500
Loading default values (write 9999)
R/W
0
510
Setpoints storing time in eeprom (0-60 s)
R/W
10
999
Process subjected to the visualization filter
RO
-
1000
Process (degrees.tenths for temperature sensors;
digits for linear sensors)
RO
-
1001
Setpoint 1
R/W
EEPROM
1002
Setpoint 2
R/W
EEPROM
1003
Setpoint 3
R/W
EEPROM
1004
Setpoint 4
R/W
EEPROM
1005
Alarm 1
R/W
EEPROM
1006
Alarm 2
R/W
EEPROM
1008
Setpoint gradient
RO
EEPROM
1009
Relay status (0 = Off, 1 = On):
Bit 0 = Relay Q1
Bit 1 = Relay Q2
Bit 2 = Reserved
Bit 3 = SSR
RO
0
1010
Heating output percentage (0-10000)
RO
0
1011
Cooling output percentage (0-10000)
RO
0
1012
Alarms status (0 = None, 1 = Active)
Bit 0 = Alarm 1
Bit 1 = Alarm 2
RO
0
1013
Manual reset: write 0 to reset all alarms.
In reading (0 = Not resettable, 1 = Resettable)
Bit 0 = Alarm 1
Bit 1 = Alarm 2
WO
0