User manual
- DRR245 31
Modbus
Address
Description
Read
Only
Reset
value
3023
Relay state in case of off-line
(only if controlled by serial)
Bit 0 = Relay Q1
Bit 1 = Relay Q2
R/W
0
3024
Output state SSR / 0..10 V / 4..20 mA in case of
off-line (only if controlled by serial)
(0..10000)
R/W
0
3025
Serial process. Setting parameter 54 it is possible
to make averages on the remote process
R/W
0
4001
Parameter 1***
R/W
EEPROM
4002
Parameter 2***
R/W
EEPROM
4072
Parameter 72***
R/W
EEPROM
* If value is 0, the control is disabled. If different from 0, it is the max. time which can elapse
between two pollings before the controller goes off-line. If it goes off-line, the controller
returns to Stop mode, the control output is disabled but the alarms are active.
** By writing 1 on this word, the effects of the writing are cancelled on all the Modbus addresses
from 3001 to 3022. Control therefore returns to the controller.
*** Parameters modified using serial address 4001 to 4072 will be stored on eeprom only after 10”
since last writing of one parameter.