60 - ATR244 -
User manual
GROUP U -
a.o. 2
- Retransmission 2
308
rtM.2
Retransmission 2
Retransmission for output AO2. Parameters 310 and 311 define lower and upper limit of the
operating scale.
diSab.
Disabled (
Default
)
c.1.SPv
Command 1 setpoint
AL. 1
Alarm 1 setpoint
AL. 2
Alarm 2 setpoint
Md.bus
Retransmits the value written on word 1242
A.iN.1
Value read on input AI1
A.in.2
Value read on input AI2
MEAn
Arithmetic average of the value read on inputs AI1 and AI2 [(AI1+AI2)/2]
diFF.
Difference of the values read on inputs AI1 and AI2 (AI1-AI2)
Ab.dif.
Module of the difference of the values read on inputs AI1 and AI2 (|AI1-AI2|)
SuM
Sum of values read on inputs AI1 and AI2 (AI1+AI2)
c.2.SPv
Command 2 setpoint
AMPer.
Ampere from current transformer
309
r.2.ty.
Retransmission 2 Type
Selects the retransmission type for AO2
0.10 v
Output 0...10 V.
4.20ma
Output 4...20 mA.
Default
310
r.2. L.L.
Retransmission 2 Lower Limit
Retransmission 2 lower limit range (value related to 10 V or 0/4 mA).
-9999..+30000 [digit
1 p. 65
] (degrees if temperature),
Default
: 0.
311
r.2. u.L.
Retransmission 2 Upper Limit
Retransmission 2 upper limit range 2 (value related to 10 V or 20 mA).
-9999..+30000 [digit
1 p. 65
] (degrees if temperature),
Default
: 1000.
312
r.2.s.e.
Retransmission 2 State Error
Determines retransmission 2 value in case of error or anomaly.
If the retransmission output is 0-10V:
0 V
0 V.
Default
10 v
10 V.
If the retransmission output is 0-20 mA or 4-20 mA:
0 ma
0 mA.
Default
4 ma
4 mA.
20 ma
20 mA.
21.5ma
21.5 mA.
313
÷317
Reserved Parameters - Group U
Reserved parameters - Group U