42 - ATR244 -
User manual
147
A.2.L.L.
Alarm 2 Lower Limit
Lower limit selectable for the alarm 2 setpoint.
-9999..+30000 [digit
1 p. 65
] (degrees for temp. sensors).
Default
0.
148
A.2.u.L.
Alarm 2 Upper Limit
Upper limit selectable for the alarm 2 setpoint
-9999..+30000 [digit
1 p. 65
] (degrees for temp. sensors).
Default
1750.
149
a.2.re.
Alarm 2 Reset
Alarm 2 contact reset type
A. rEs.
Automatic reset (
Default
)
M. rEs.
Manual reset (manual reset by keyboard or by digital input)
M.rEs.S.
Stored manual reset (keeps the output status also after a power failure)
150
A.2.S.e.
Alarm 2 State Error
Alarm 2 output status in case of error
If the alarm output is relay
open
Contact or open valve.
Default
CLose
Contact or closed valve.
If the alarm output is digital (SSR):
off
Digital output OFF.
Default
on
Digital output ON.
151
A.2.Ld.
Alarm 2 Led
Defines the status of the led
A2
in correspondence of the relevant output.
o.c.
ON with open contact or DO switched off.
c.c.
ON with closed contact or DO switched on. (
Default
)
152
a.2.de.
Alarm 2 Delay
Alarm 2 Delay.
-3600..+3600 seconds.
Default
: 0.
Negative value: delay when exit alarm status.
Positive value: delay when enter alarm status
153
A.2.S.p.
Alarm 2 Setpoint Protection
Allows or not to change the alarm 2 setpoint
FrEE
Editable by the user (
Default
)
Lock
Protected
HidE
Protected and not visualized
154
A.2.Lb.
Alarm 2 Label
Selects the message to be visualized in case of alarm 2 intervention
0 Disabled.
Default
0.
1-20
Message 1..20 (see customizable messages table)
155÷158
Reserved Parameters - Group H
Reserved parameters - Group H