16 - ATR244 -
User manual
switched to RUN, otherwise is kept in STOP;
•
t.1.s.e.
: If timer 1 is enabled (par. 328
tmr.1
different from
disab.
), acting on the digital input, the status
of the timer switches from STOP to RUN e vice versa;•
t.1.sta.
: If il timer 1 is enabled (par. 328
tmr.1
differnet from
disab.
), acting on the digital input, the timer is switched to RUN;
•
t.1.end.
: If il timer 1 is enabled (par. 328
tmr.1
differnet from
disab.
), acting on the digital input, the
timer is switched to STOP;
•
t.2.run
: If timer 2 is enabled (par. 331
tmr.2
different from
disab.
), with digital input active, the timer
is switched to RUN, otherwise is kept in STOP;
•
t.2.s.e.
: If timer 2 is enabled (par. 331
tmr.2
different from
disab.
), acting on the digital input, the
status of the timer switches from STOP to RUN e vice versa;
•
t.2.sta.
: If timer 2 is enabled (par. 331
tmr.2
different from
disab.
), acting on the digital input, the
timer is switched to RUN;
•
t.2.end.
: If timer 2 is enabled (par. 331
tmr.2
different from
disab.
), acting on the digital input, the
timer is switched to STOP;
•
Lo.cfG.
: With digital input active, the access to setpoint configuration/modification is locked;
•
reM.s.e.
: If on par. 56
rem.s.
it is selected
enab.
or
en.ser.
), with digital input active the remote setpoint
is enabled, otherwise the setpoint is local. On par. 234
d.i.1.r.
or 242
d.i.2.r.
or 250
d.i.3.r.
or 258
d.i.4.r.
it is necessary to select the reference regulation loop.
8.7
Automatic / Manual regulation for % output control
This function allows to switch from automatic functioning to manual command of the output
percentage.
With par. 48
A.ma.1.
(for regulation loop 1) or par. 67
A.ma.2.
(for regulation loop 2) it is possible to select
two modes.
1 First selection
(
enab.
) allows to eneble with
FNC
the writing
p.---
on display 1, while on display 2 is
showed
autom.
Press
SET
to visualize
manu.
; it’s now possible, during the process visualization, modify through the
keys
c
and
d
the output percentage. To back to automatic, with the same procedure, select
autom.
on display 2: immediately led
MAN
switches off and functioning backs to automatic.
2 Second selection
(
en.sto.
) enables the same functioning but with two important variants:
• If there is a temporary power failure or after switch-off, the manual functioning as well as the
previous output percentage value will be maintained at restarting.
• If the sensor breaks during automatic functioning, the controller switches to manual mode while
maintaining the output percentage command unchanged as generated by the PID immediately
before breakage.
Ex: on an extruder the command in percentage of the resistance (load) is maintained also in case of
input sensor failure.
8.8
Heater Break Alarm on CT (current transformer - only
on ATR244-23xx-T)
This function allows to measure load current to manage an alarm during a malfunctioning with power
in short circuit, always open or partial break of the charge. To enable this function set
50 Hz
or
60 Hz
on
par. 287
ct F.
and the value of the connected transfomer, on par. 288
ct v.
.
• Seletct on par. 289
H.b.a.r.
the regulation loop referred to the current measure and the Heater Break
Alarm intervention.
• Select on par. 290
H.b.a.t.
the Heater Break Alarm intervention threshold in Ampere.
• Select on par. 291
ocu.t.
the intervention threshold in Ampere to control the overcurrent.
• Select on par. 292
H.b.a.d.
the delay time in seconds for the Heater Break Alarm intervention.
• It is possible to associate an alarm, selecting
H.b.a.
on par. 123
aL.1.F.
on par. 141
aL.2.F.
or par. 159
aL.3.F.
or par. 177
aL.4.F.
or par. 195
aL.5.F.
or par. 213
aL.6.F.
It is possible to visualize on display 2 the average current, selecting
AMPEr.
on par. 278
vi.d.2
.
Selecting 0 on par. 290
H.b.A.t.
it is possible to visualize the current consumption without generating
an Heater Break Alarm.