54 - ATR244 -
User manual
GROUP P -
d.i. 4
- Digital input 4
255
d.i.4.f.
Digital Input 4 Function
Digital input 4 functioning.
diSab.
Disabled (
Default
)
2t. sw.
2 Setpoints Switch
2t.sw.i.
2 Setpoints Switch Impulsive
3t.sw.i.
3 Setpoints Switch Impulsive
4t.sw.i.
4 Setpoints Switch Impulsive
st./st.
Start / Stop
rUn
Run
HoLd
Lock conversion (stop all conversions and display values)
tune
Performing manual tune
au.ma.i.
Automatic / Manual Impulse (if enabled on parameter 48 or 67)
au.ma.c.
Automatic / Manual Contact (if enabled on parameter 48 or 67)
act.tY.
Action Type. Cooling regulation if D.I. is active, otherwise heating reg.
A.i. 0
Analogue Input 0. Set AI to zero
M. reS.
Manual reset. Reset the outputs if selected as manual reset.
t.1.run
Timer 1 run. The timer 1 count with activated D.I.
t.1. s.E.
Timer 1 Start End. D.I. starts and stops the timer 1(impulsive)
t.1.Sta.
Timer 1 Start. D.I. starts the timer 1(impulsive)
t.1.End
Timer 1 End. D.I. stops the timer 1(impulsive)
t.2.run
Timer 2 run. The timer 2 count with activated D.I.
t.2. s.E.
Timer 2 Start End. D.I. starts and stops the timer 2(impulsive)
t.2.Sta.
Timer 2 Start. D.I. starts the timer 2(impulsive)
t.2.End
Timer 2 End. D.I. stops the timer 2(impulsive)
Lo.cfG.
Lock configuration and setpoints.
up.key
Simulates the functioning of up key.
down.k.
Simulates the functioning of down key.
fnc. k.
Simulates the functioning of fnc key.
set. k.
Simulates the functioning of set key.
rem.s.e.
Remote setpoint enabling. Enables Remote setpoint with activated D.I. Local setpoint
with deactivated D.I. (remote setpoint must be enabled on parameter 56
rem .s .
)
256
d.i.4.c.
Digital Input 4 Contact
Defines the resting contact of the digital input 4.
n.open
Normally open (
Default
)
n.cLos.
Normally closed
257
d.i.4.P.
Digital Input 4 Process
(only on ATR244-23ABC-T)
Select the size related to the digital input 4.
A.in.1
Value read on input AI1. (
Default
)
A.in.2
Value read on input AI2.
MEAn
Arithmetic average of the value read on inputs AI1 and AI2 [(AI1-AI2)/2].
diFF.
Difference of the values read on inputs AI1 and AI2 (AI1-AI2).
Ab.dif.
Module of the difference of the values read on inputs AI1 and AI2 (|AI1-AI2|).
SuM
Sum of values read on inputs AI1 and AI2 (AI1+AI2).
258
d.i.4.r.
Digital Input 4 Reference Command
Defines the reference command for the digital input 4 functions.
cmd. 1
Command 1 (
Default
)
cmd. 2
Command 2
cmd.1.2
Command 1 and 2
259÷262
Reserved Parameters - Group P
Reserved parameters - Group P