Document 15666 Rev. D 9/19/96
7
Notes:
1. Up to 10 LIB SLC loops can be installed in a master
AM2020 or up to 4 LIB SLC loops in a master AFP1010.
2. Each LIB SLC loop can support a maximum of 12 NIB-
96 boards (@ 8 points each) or a maximum of 96 NIB
points.
3. Each NIB may be set to report as few as 8 points or as
many as 96 points.
4. See Document 15511 for a detailed configuration and
for connections for transmission to central station.
5. Each AFP-200 slave uses eight points for AFP-200
system functions. The remaining 88 NIB points can be
used in multiples of eight to display the status of AFP
zones 1 to 88.
6. The Master can not activate AFP zones.
7. The Master can perform the following functions:
Signal Silence via point #2, System Reset via point #3
and 'Drill' via point #4 (Drill requires NIB software 73454
or higher).
8. The Ground Fault circuit in the AFP-200 must be
disabled by cutting jumper JP9 unless an RPT-485
series repeater is used to isolate the AFP-200 from the
AM2020/AFP1010 (refer to Document #15640).
Master AM2020/AFP1010
System Common
EIA-485
AFP-200 Slave
ö
ö
ö
ö
ö
Figure 2-2 Master AM2020/AFP1010-Slave AFP-200 Configuration
(Refer to Table 1-2 for circuit ratings)