![Pittway Notifier NIB-96 Manual Download Page 33](http://html1.mh-extra.com/html/pittway/notifier-nib-96/notifier-nib-96_manual_1560287033.webp)
Document 15666 Rev. D 9/19/96
33
Appendix C:
Network Requirements for ULC listed Panels
NIB-96 network installations requiring Underwriter's Laboratories of
Canada listing must follow the guidelines set forth in this appendix.
In Canada, slave control panels must be able to function as stand-alone units dur-
ing loss of communications with the master control panel. Therefore, each slave
panel must be programmed for complete local input/output operation.
If the master control panel is to also control output circuits in the slave panels, care
must be taken to ensure that programming in both the master and the slave(s) is
identical.