Document 15666 Rev. D 9/19/96
28
Size Settings
The setting of the rotary decimal SIZE switch on the NIB determines the number of
AFP-200 zones that will be reported to the Master AM2020/AFP1010. Use Table
10-1 to determine the required setting for the SIZE switch.
SW2:
SIZE Switch
SW3 and SW4:
START ADDRESS
Switches
Table 10-1 SIZE Switch Settings
Start Address Settings
The START ADDRESS switches are set for the desired address from the master
SLC loop. The NIB will answer all module addresses from (START ADDRESS) to
(START A SIZE -1) inclusive.
Note that the total of START A SIZE - 1 must be 96 or less for the NIB
to operate.
START A SIZE - 1 < 96
DIP Switch Settings
Refer to Table 1-3 for the recommended AFP-200 slave DIP switch settings.
Switch
Setting
Information Sent to Master
Size
(Points)
1
System Status
8
2
System Status plus Zones 1 to 18
16
3
System Status plus Zones 1 to 16
24
4
System Status plus Zones 1 to 24
32
5
System Status plus Zones 1 to 32
40
6
System Status plus Zones 1 to 40
48
7
System Status plus Zones 1 to 48
56
8
System Status plus Zones 1 to 56
64
9
System Status plus Zones 1 to 72
80
0
System Status plus Zones 1 to 88
96