Document 15666 Rev. D 9/19/96
27
No connection on
P2 or P3 if ICA-4/4L
chassis is used.
P2
P3
NIB-96
Electrical Installation
If the NIB is mounted to a CHS-4...
Connect the main power harness from the MPS power supply to P3 on the NIB.
Connect the short power harness (provided) from P2 on the NIB to the ICA-4/4L If
additional NIBs are installed, the power harness is daisy-chained through all NIBs.
If the NIB is mounted to an ICA-4/4L...
All power connections are completed through the ICA-4/4L connection.
Referring to the terminal assignment table below, connect the EIA-485 input on the
NIB to the EIA-485 connector on the slave AFP-200. If the slave AFP-200 also has
annunciators, the EIA-485 OUT terminals on the NIB are used to daisy-chain to
these additional EIA-485 devices.
Connect the LIB SLC loop from the master AM2020/AFP1010 to the NIB's SLC in-
put terminals. Typically, each NIB is connected to a single LIB in the master
AM2020/AFP1010 and uses almost all of the module capacity (96 out of 99 maxi-
mum) of that LIB SLC.
Figure 10-2 Wiring the NIB/AM2020/AFP1010/AFP-200 Network
SLC loop
Out
SLC loop
IN
EIA-485 Loop OUT
To additional EIA-485 devices, if installed.
EIA-485 Loop
to AFP-200
TB5-1 (+)
TB5-2 (-)
EIA-485
Loop IN
Terminal Assignments
SLC Loop IN
From: Master LIB (LIB-200 P2 terminals 1(+) and 3(-), LIB-200A TB1
terminals 1(+) and 3 (-), LIB-400 TB1 or TB2 terminals 1(+) and 3(-))
To: NIB-96 P5 terminals 1(+) and 3(-)
EIA-485 Loop IN
From: AFP-200 TB5 terminals 1(+) and 2(-)
To: NIB-96 P4 terminals 5(+) and 3(-)
SLC Loop Out
From: NIB-96 P5 terminals 5(+) and 7(-)
To: Next device on SLC Loop
EIA-485 Loop OUT
From: NIB-96 P4 terminals 6(+) and 4(-)
To: Next device on EIA-485 Loop