Document 15666 Rev. D 9/19/96
15
CPU-5000
Figure 4-2 Wiring the NIB/System 5000 Slave Network
(Refer to Table 1-2 for circuit ratings)
SIZE Setting Table
(Printed in the lower
left-hand corner of
the NIB-96 board.)
P2
MPS-24A/E or
MPS-24B/E
EIA-485 Loop
OUT to other
annunciators
(if used)
Main Power
Harness
#71086.
Main Power Harness
(P/N 75099)
P2
P3
NIB-96
EIA-485 Loop
- +
TB2
J7
SLC Loop IN
SLC Loop OUT
Size Settings
The rotary decimal SIZE switch on the NIB sets the capacity of the System 5000.
The size corresponds to the number of slave circuits that the master control panel
will monitor as individual points. The SIZE of the System 5000 is usually eight times
the number of modules installed, including the CPU.
Note: All connections shown are
power limited
Switch Setting
No. of Points
1
8
2
16
3
24
4
32
5
40
6
48
7
56
8
64
9
80
0
96
Terminal Assignments
SLC Loop IN
From: AIM-200 SLC Loop Out
To: NIB-96 P5 terminals 1(+) and 3(-)
EIA-485 Loop IN
From: CPU-5000 TB2 terminals 2(+) and 1(-)
To: NIB-96 P4 terminals 5(+) and 3(-)
SLC Loop Out
From: NIB-96 P5 terminals 5(+) and 7(-)
To: Next device on SLC Loop
EIA-485 Loop OUT
From: NIB-96 P4 terminals 6(+) and 4(-)
To: Next device on EIA-485 Loop
Technical Manuals Online! - http://www.tech-man.com