SERVICE
22
L22-236 Rev. 2 (06/11)
4. For Split Tank Gas Valves:
a. Loosen and disconnect top valve flare
fitting from burner manifold using 1-1/16”
open end wrench on female brass flare
fitting at top of valve and15/16” open end
wrench on male brass flare fitting attached
to burner manifold
b. Move valve forward to access supply
tubing at bottom of valve.
c. Loosen and remove gas supply tubing at
bottom of valve using 1-1/16” open-end
wrench on tubing end connector, and
remove valve from fryer.
5. Remove brass quick disconnect fittings from
Gas Valve using 15/16” open end wrench on
male flare fitting at bottom of valve, and 7/8”
thin open end wrench on male end of female
fitting at top of valve.
6. For Full Tank valves, remove screw securing
heat shield to valve using 1/4” socket.
7. Straighten and remove vent tubing.
8. Installation is reverse of removal. Be sure to
re-install heat shield on valve.
9. Leak test all gas fittings after re-assembly
using an appropriate leak detection fluid.
WARNING! SHUT OFF APPLIANCE AND DISCONNECT ALL POWER
CONNECTIONS PRIOR TO STARTING ANY SERVICE WORK
WARNING! DISCONNECT APPLIANCE FROM GAS SUPPLY OR SHUT
MANUAL GAS VALVE PRIOR TO SERVICING GAS TRAIN