NEVER LEAVE HEATER UNATTENDED WHILE BURNING 

OR WHILE CONNECTED TO A POWER SOURCE

© 2017, Pinnacle Climate Technologies, Inc. 

Kerosene Forced Air Heater User’s Manual 

Maintenance

Service (Continued):
SPARK PLUG:

Clean and re-gap every 600 hours of operation, or 

replace as needed. After removing the spark plug, 

clean the terminals with a wire brush. Re-gap the 

terminals to 0.140” (3.5mm) See Figure 5.

PHOTOCELL:

The photocell should be cleaned using a cotton 

swab dipped in alcohol or water at least once per 

heating season, or more depending on conditions. 

See Figure 6.

PUMP PRESSURE:

While heater is operating, turn adjusting screw 

clockwise to increase, counter-clockwise to 

decrease pressure. Correct pump pressure is as 

follows: 

Model Number

Pump Pressure

45-KFA

3.0 PSI

75T-KFA

4.2 PSI

135T-KFA

5.5 PSI

175T-KFA

7.5 PSI

190T-KFA

8.5 PSI

215T-KFA

9.0 PSI

Tolerance ± 10%

NOZZLES:

Nozzles should be cleaned or replaced at least 

once per heating season. Contaminated fuel could 

make this necessary immediately. To clean dirt 

from nozzle, blow compressed air through nozzle 

front. It may be necessary to soak the nozzle in K-1 

kerosene to loosen any dirt particles.

Figure 5

Ignitor Wire

Spark Plug

Gap

Burner Head

Figure 6

X

X

Photocell

Photocell lens

Photocell 

Wire

8

Figure 8

Adjusting Screw

Pressure Valve

Figure 7

Nozzle

Nozzle Face

Burner Head

Summary of Contents for Remington REM-135T-KFA-O

Page 1: ...to Ventilation on Page 5 FACTORY ID 001 Safety Information FIRE BURN INHALATION AND EXPLOSION HAZARD Keep combustibles such as building materials paper or cardboard a safe distance away from the heate...

Page 2: ...use for temporary heating of buildings under construction alteration or repair Direct fired means that all of the combustion products of the heater enter the heated space This appliance is rated at 98...

Page 3: ...ls away from this heater Minimum Clearance From Combustibles 45 190T KFA 215T KFA Top 4 ft 4 ft Sides 4 ft 4 ft Front 8 ft 10 ft ALWAYS locate heater on a stable and level surface If your heater is eq...

Page 4: ...Manual 3 Wiring Diagrams 45 KFA 75T 215T KFA Assembly Instructions What s In The Box Models 45 KFA 75T KFA Remove the heater and all packaging materials from the shipping carton Note Save the box and...

Page 5: ...lace heater on wheel support and line up holes on the fuel tank lip 5 Attach front handle with 2 long screws 50 mm and 2 nuts through the second hole from the front on both sides of the tank lip and w...

Page 6: ...R use kerosene that has been stored from one season to the next Kerosene deteriorates over time OLD KEROSENE WILL NOT BURN PROPERLY IN THIS HEATER NOTE Kerosene should only be stored in a blue contain...

Page 7: ...temperature display will indicate the following When the temperature is less than 0 F the display says LO When the temperature is more that 99 F the display says HI Between 0 F and 99 F the display s...

Page 8: ...starting the heater FUEL FILTER The fuel filter should be cleaned at least twice per heating season Clean the filter by rinsing it in clean K 1 Kerosene Contaminated fuel could make cleaning the fuel...

Page 9: ...ESSURE While heater is operating turn adjusting screw clockwise to increase counter clockwise to decrease pressure Correct pump pressure is as follows Model Number Pump Pressure 45 KFA 3 0 PSI 75T KFA...

Page 10: ...proper spacing with rotor 1 Fill tank with fresh kerosene 2 Adjust pump pressure 3 Clean replace spark plug 4 Clean replace fuel filter 5 Clean replace nozzle 6 Rinse fuel tank with clean fresh kerose...

Page 11: ...POWER SOURCE 2017 Pinnacle Climate Technologies Inc Kerosene Forced Air Heater User s Manual 10 14 11 13 8 12 9 30 26 3 16 2 4 6 1 7 22 24 17 18 19 21 30 20 15 41 33 35 36 29 28 5 32 31 25 27 38 37 3...

Page 12: ...21 0510 70 021 0520 70 021 0520 18 Pump Body 70 020 0101 70 020 0101 70 020 0101 70 020 0401 70 020 0401 19 Rotor Kit 70 022 0100 70 022 0100 70 022 0100 70 022 0200 70 022 0200 20 End Pump Cover 70 0...

Page 13: ...If Pinnacle Climate Technologies Inc finds the item to be in normal operating condition or not defective the item will be returned freight collect This Limited Warranty is in lieu of all other expres...

Page 14: ...1 Industrial Blvd 101 Sauk Rapids MN 56379 USA Toll Free 866 676 1989 Fax 320 251 2922 Web www remingtonheater com Email info pinnacleclimate com 2017 Pinnacle Climate Technologies Inc...

Reviews: