background image

1

50ZPB, C, D, 50ZHB, C,

PA3Z---A, PH3Z---A, PA4Z, PH4Z,

PAJ4, PHJ4, WJA4, WJH4

Installation Instructions

SMALL PACKAGED PRODUCTS (SPP)

Accessory Electric Heaters 5---20 kW

For 14 SEER, R---410A

Manufactured Home

NOTE

:

The Dual Point Kit can only be installed on units

equipped with a 2

nd

electrical entry (knockout), the knockout was

added to the electrical panel starting with the following unit serial
numbers:
2711X_ _ _ _ _ and later
X1127_ _ _ _ _ and later

NOTE

: Read the entire instruction manual before starting the

installation.

NOTE

: Installation Instructions include Single and Dual point

connection instructions separately.

SAFETY CONSIDERATIONS

Improper installation adjustment, alteration, service, maintenance,

or use can cause explosion, fire, electrical shock, or other

conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your

distributor or branch for information or assistance. The qualified
installer or agency must use factory--authorized kits or accessories

when modifying this product Refer to the individual instructions

packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,

and work gloves. Use quenching cloth for brazing operations.
Have a fire extinguisher available. Read these instructions

thoroughly and follow all warnings or cautions included in

literature and attached to the unit. Consult local building codes, the
current editions of the National Electrical Code (NEC) NFPA 70.
In Canada refer to the current editions of the Canadian Electrical
Code CSA C22.1.
Recognize safety information. This is the safety--alert symbol

.

When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand

these signal words; DANGER, WARNING, and CAUTION. These

words are used with the safety--alert symbol. DANGER identifies
the most serious hazards which

will

result in severe personal injury

or death. WARNING signifies hazards which

could

result in

personal injury or death. CAUTION is used to identify unsafe

practices which

may

result in minor personal injury or product and

property damage. NOTE is used to highlight suggestions which

will

result in enhanced installation, reliability, or operation.

Before proceeding with heater installation, inspect thoroughly for
shipping damage. Notify shipper immediately if any damage is

found. Clean all dirt, dust and moisture from heater package.
Check for proper clearances of live parts, between phases and to

ground. Make sure that all required barriers are in place. Check

conductors run in multiple to insure that they are properly wired.
Refer to unit installation instructions for complete unit installation

details. The minimum air quantity for safe electric heater operation
is shown in Table 2.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before performing installation, service or maintenance

operations on this system, turn off all main power to system.

There may be more than one disconnect switch. Turn off

accessory heater power switch if applicable. Lock out and

tag switch with a suitable warning label.

!

WARNING

DESCRIPTION AND USAGE

These heaters are comprised of a separate heater module mounted

on the blower inlet and remote mounted controls located in the unit
control box. Heater models are provided with single point electrical

connections for powering both the heater and the unit.
These heaters are intended for use only in SPP units as noted in
Table 1.

PACKAGE CONTENTS

Electric Heater Package Contents

1. Heater assembly, comprised of heater module and control

panel

2. UPC heater label
3. Installation Instructions
4. Identification label
5. Wiring label
6. Wire connectors (2)
7. Wire tires--6” (5)
8. Screws #10B (4)
9. Ground lug (1) (See Fig. 8)

10. Bolts 3/8--16 (3)
11. Plug attachment plate
12. Dual Point Electric Rating Label
13. Dual Point Warning Label

INSTALLATION

Single Point Heater Installation

1. Open all electrical disconnects and install lock--out tag

before beginning any installation or service work.

2. Check for proper heater application in Table 1.
3. Remove unit side panel to access blower compartment (See

Fig. 1 and Fig. 2).

4. Disconnect wiring to motor by removing speed selection

and power plugs from bottom of motor (See Fig. 2).

5. Remove rear blower support bracket. Remove shipping

block and label under blower if unit has one (See Fig. 2).

6. Remove screws securing blower to front blower support

bracket; slide blower out of unit.

Summary of Contents for 50ZPB

Page 1: ...erty damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation Before proceeding with heater installation inspect thoroughly for shipping damage Notify shipper immediately if any damage is found Clean all dirt dust and moisture from heater package Check for proper clearances of live parts between phases and to ground Make sure that all require...

Page 2: ... in heater wiring plug attachment plate installed in step 9 above See Fig 4 13 Rotate heater control panel into unit control box area and locate it into top left corner of control box secure heater control panel to unit control box with 4 screws provided See Fig 6 14 Open flexible fishpaper insulation cover provided with unit control box and route heater low voltage wires along the bottom of the u...

Page 3: ...let Stage 1 Stage 2 125A03 110070151 3 75 5 208 230 1 60 18 20 8 x 1 x x 5kw 126A03 110070152 3 75 5 18 20 8 x 1 x x 5kw 127A03 110070153 5 6 7 5 27 31 3 x 1 x x 7 5kw 128A03 110070154 5 6 7 5 27 31 3 x 1 x x 7 5kw 129A03 110070155 7 5 10 36 1 41 7 x 1 x x 10kw 130A03 110070156 7 5 10 36 1 41 7 x 1 x x 10kw 131A03 110070157 11 3 15 54 1 62 5 x 2 x x x 5kw 10kw 132A03 110070158 15 20 72 1 83 3 x 2 ...

Page 4: ...NG LABEL ELECTRICAL RATING LABEL LOCATION BLOWER ACCESS PANEL ELECTRICAL PANEL KNOCKOUT HOLE FOR DUAL POINT A11167 Fig 1 Access Panel and Label Location BLOWER MOTOR BLOWER SUPPORT BRACKET SPEED SELECTOR POWER PLUG A05382 Fig 2 Indoor Blower Compartment CPHEATER ...

Page 5: ...5 HEATER MODULE BOLTS 3 A10111 Fig 3 Attach Heater Module HEATER WIRING PLUG ATTACHMENT PLATE WITH PLUG INSTALLED COVER PLATE A05384 Fig 4 Inside Blower Compartment CPHEATER ...

Page 6: ...nection electric heater controls removed for clarity Electric Heat Control Box shown uninstalled A10031 Fig 5 Unit Control Box Compartment HEATER CONTROL PANEL MOUNTING SCREWS 4 A10119 Fig 6 Heater Control Panel Installation CPHEATER ...

Page 7: ...d service HEATER RELAY LOW VOLTAGE WIRES A10120 Fig 7 Heater Low Voltage Connection GROUND LUG SINGLE POINT CONNECTION LOW VOLTAGE WIRING COMPARTMENT FISH PAPER POWER SUPPLY FOR CONTACTOR FIELD HIGH VOLTAGE SUPPLY A10121 Fig 8 Unit Power Connection CPHEATER ...

Page 8: ...ctrical disconnects and install lockout tag before beginning any installation or service work 2 Remove Control Box Access Panel see Fig 1 check for clearance on the inside of control box and remove a 7 8 in knockout hole on the Electrical Panel for second power line 3 Attach warning and rating labels in the selected location see Fig 1 4 Mark the main unit nameplate with an X next to the accessory ...

Page 9: ...uncut the time delay is approximately 5 sec after the initial first stage When jumper is cut at factory this provides an 8 sec delay 1 Refer to base unit installation instructions as required 2 Check for loose terminal connections 3 Check that all fuse and circuit breaker short circuit interrupting ratings are adequate 4 Turn on unit and heater power 5 Set thermostat to call for heat 6 Check opera...

Page 10: ...IELD POWER LINE TO UNIT CONTACTOR FIRST FIELD POWER LINE TO HEATER 24V FIELD WIRING BOX A10379 Fig 12 Dual Point Connections For Heater With Circuit Breaker 24V FIELD WIRING BOX SECOND FIELD POWER LINE TO UNIT CONTACTOR FIRST FIELD POWER LINE TO HEATER A10382 Fig 13 Dual Point Connections For Heaters Without Circuit Breakers CPHEATER ...

Page 11: ...N TO UNIT POWER WIRING Wires for single point connection only Remove wires for dual point connection Replace Thermal Cut out with Therm O Disc type G8AM0402110C HR1 HK61EA033 W1 QC1 TP2 TP1 QC2 D2 QC2A QC1A D1 D4 D3 Pb SST B 1 e 24VDC 24VDC CEBD430344 06 RB US C HSCI CEPL130344 02 R 1 2 W1 TO UNIT CONTROL WIRING N E C Class 2 24V Replace Relay with T92 22VDC BLACK BLACK YELLOW L2 L1 3 75 5 0 CPHEA...

Page 12: ...ING HR1 HK61EA033 W1 QC1 TP2 TP1 QC2 D2 QC2A QC1A D1 D4 D3 Pb SST B 1 e 24VDC 24VDC CEBD430344 06 RB US C HSCI CEPL130344 02 R 1 2 W1 TO UNIT CONTROL WIRING N E C Class 2 24V Replace Relay with T92 22VDC L2 L1 OFF OFF CB 1 CB 2 ON ON 50 A 30 A 3 75 5 0 CPHEATER126A03 110070152 208 240 1 60 24 AC 1 18 0 20 8 50A 30A BLACK BLACK YELLOW EL1 AUTO LIMIT Wires for single point connection only Remove wir...

Page 13: ... HR1 HR2 HK61EA033 W1 QC1 TP2 TP1 QC2 D2 QC2A QC1A D1 D4 D3 Pb SST B 1 e 24VDC 24VDC CEBD430344 06 RB US C HSCI CEPL130344 02 R 1 2 W1 TO UNIT CONTROL WIRING N E C Class 2 24V Replace Relay with T92 22VDC L2 L1 BLACK BLACK BLACK CPHEATER127A03 110070153 5 6 7 5 208 240 1 60 24 AC 1 27 0 31 3 BROWN WHITE BLACK BLACK YELLOW YELLOW Wires for single point connection only Remove wires for dual point co...

Page 14: ...D4 D3 Pb SST B 1 e 24VDC 24VDC CEBD430344 06 RB US C HSCI CEPL130344 02 R 1 2 W1 TO UNIT CONTROL WIRING N E C Class 2 24V Replace Relay with T92 22VDC L2 L1 OFF OFF CB 1 CB 2 ON ON 50 A 60 A 5 6 7 5 CPHEATER128A03 110070154 208 240 1 60 24 AC 2 27 0 31 3 50A 60A WHITE BROWN BLACK YELLOW BLACK BLACK YELLOW BLACK EL1 AUTO LIMIT Control Wiring Power Wiring Field Wiring Wires for single point connecti...

Page 15: ...1 QC2 D2 QC2A QC1A D1 D4 D3 Pb SST B 1 e 24VDC 24VDC CEBD430344 06 RB US C HSCI CEPL130344 02 R 1 2 W1 TO UNIT CONTROL WIRING N E C Class 2 24V Replace Relay with T92 22VDC L2 L1 BLACK BLACK BLACK 7 5 10 0 208 240 1 60 24 AC 1 36 1 41 7 BLACK BLACK YELLOW YELLOW WHITE BROWN EL1 AUTO LIMIT Control Wiring Power Wiring Field Wiring Wires for single point connection only Remove wires for dual point co...

Page 16: ...4 D3 Pb SST B 1 e 24VDC 24VDC CEBD430344 06 RB US C HSCI CEPL130344 02 R 1 2 W1 TO UNIT CONTROL WIRING N E C Class 2 24V Replace Relay with T92 22VDC L2 L1 OFF OFF CB 1 CB 2 ON ON 50 A 60 A 7 5 10 0 CPHEATER130A03 110070156 208 240 1 60 24 AC 1 36 1 41 7 50A 60A WHITE BROWN BLACK BLACK YELLOW YELLOW BLACK BLACK EL1 AUTO LIMIT Control Wiring Power Wiring Field Wiring Wires for single point connecti...

Page 17: ...N E C Class 2 24V Replace Relay with T92 22VDC 11 3 15 0 CPHEATER131A03 110070157 208 240 1 60 24 AC 30A 2 54 1 62 5 50A 60A BLACK BLACK BLACK BLACK BLACK BLACK YELLOW YELLOW YELLOW YELLOW YELLOW YELLOW BROWN HK61EA034 W2 TP1 TP2 QC1 QC2 R2 D1 D3 D2 D4 D5 R1 R3 R4 C2 C1 Z1 Z2 Q1 QC1A QC2A Q2 Pb SST B 1 e 24VDC 24VDC CEBD430345 06 RB US C HSCI VIOLET EL1 AUTO LIMIT Control Wiring Power Wiring Field...

Page 18: ... QC2A Q2 Pb SST B 1 e 24VDC 24VDC CEBD430345 06 RB US C HSCI 1 TO UNIT CONTROL WIRING N E C Class 2 24V Replace Relay with T92 22VDC BLACK BLACK YELLOW BLACK YELLOW YELLOW YELLOW BLACK BLACK BLACK BLACK WHITE BROWN BROWN VIOLET Control Wiring Power Wiring Field Wiring Wires for single point connection only Remove wires for dual point connection Replace Thermal Cut out with Therm O Disc type G8AM04...