Wiring the Inputs and Outputs
7-10
Operating Manual: PSS 3075-3 Series
Example: Single-channel, failsafe input device, with test pulse
Features:
• Depending on the application area and its respective regulations, this
connection diagram is suitable for applications up to category 2 in
accordance with EN 954-1.
• The input device must be approved for failsafe applications.
• Please read the instructions provided with the input device.
• The test pulse must be allocated to the input in the system software’s
PSS Configurator (e.g. PSS WIN-PRO).
• Testing will detect short circuits on the input device cable to L+ and to
other test pulses.
• Only input devices with N/C contacts can be tested.
• Cable runs: 1 ms inputs: 200 m
With 1 kOhm resistance parallel to input: max. 800 m
CAUTION!
Short circuits between the cable from the signal to the input device and the
cable from the input device to the input will not be detected.
Summary of Contents for PSS 3075-3 Series
Page 1: ...Programmable control systems PSS PSS 3075 3 Series Operating Manual Item No 21 071 10 ...
Page 13: ...2 3 Operating Manual PSS 3075 3 Series Notes ...
Page 28: ...Overview 2 18 Operating Manual PSS 3075 3 Series Notes ...
Page 46: ...Installation 5 6 Operating Manual PSS 3075 3 Series Notes ...
Page 72: ...Wiring the Inputs and Outputs 7 22 Operating Manual PSS 3075 3 Series Notes ...
Page 86: ...Operation and Maintenance 9 6 Operating Manual PSS 3075 3 Series Notes ...
Page 94: ...Technical Details 10 8 Operating Manual PSS 3075 3 Series Notes ...
Page 98: ...Appendix 11 4 Operating Manual PSS 3075 3 Series Notes ...