10-3
Operating Manual: PSS 3075-3 Series
Inputs and outputs
Polarity protection
Galvanic isolation
Status display
Inputs
Number
Signal level at “0”
Signal level at “1”
Input current
Input delay
Pulse suppression
Alarm detection time
Outputs - single-pole
Number
Output current at “1”
without UL approval
with UL approval
Short circuit protection
Limitation of inductive switch-off
Residual current at “0” Signal
Signal level at “0”
Signal level at “1”
Switch-off delay
On time during self test
Off time during self test
Yes
Yes (optocoupler)
LED
48, 6 of which are alarm inputs
-3 ... +5 VDC
+15 ... +30 VDC
Typ. 6 mA
< 1 ms, alarm inputs: 0.5 ms
≤
300 µs
(requirement: in the PSS Configurator,
≥
3 ms must be configured under “Max.
delay of digital inputs” and “DI test time”.)
Alarm inputs that do not use test pulses: 2 ms
Alarm inputs that use test pulses: 3 ms
18, 4 of which are test pulse outputs
Max. 3,5 A (see Derating diagrams)
Max. 1,5 A
Electronic
Test pulses: ca. UB -42 VDC
Single-pole outputs: ca. UB -70 VDC
0 mA
0 VDC
U
B
-1 VDC at 3.5 A
Test pulses: ca. 50 µs
Single-pole outputs: < 200 µs
ca. 200 µs
400 µs ... 500 µs
Summary of Contents for PSS 3075-3 Series
Page 1: ...Programmable control systems PSS PSS 3075 3 Series Operating Manual Item No 21 071 10 ...
Page 13: ...2 3 Operating Manual PSS 3075 3 Series Notes ...
Page 28: ...Overview 2 18 Operating Manual PSS 3075 3 Series Notes ...
Page 46: ...Installation 5 6 Operating Manual PSS 3075 3 Series Notes ...
Page 72: ...Wiring the Inputs and Outputs 7 22 Operating Manual PSS 3075 3 Series Notes ...
Page 86: ...Operation and Maintenance 9 6 Operating Manual PSS 3075 3 Series Notes ...
Page 94: ...Technical Details 10 8 Operating Manual PSS 3075 3 Series Notes ...
Page 98: ...Appendix 11 4 Operating Manual PSS 3075 3 Series Notes ...