Commissioning
Operating Manual PNOZ ms4p
22109-EN-03
16
6
Commissioning
6.1
General wiring guidelines
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
Details of the input type, axis type and reset mode, plus the values for standstill, speed
monitoring and direction of rotation are also defined in the PNOZmulti Configurator.
Please note:
}
Information given in the Technical details must be followed.
}
Use copper wiring with a temperature stability of 75 °C.
CAUTION!
The configurable switch-off delay when overspeed is reached increases the
reaction time of the system comprising base unit and speed monitor by the
stated value (see technical details). This must not delay the transfer to a
safe condition by more than the permitted time. The configuration of the
switch-off delay must be considered in the risk assessment as regards haz-
ards, reaction time and safety distance.
6.2
Pin assignment of RJ45 socket
RJ45 socket
8-pin
PIN
Track
8 1
1
5 V
2
0 V
3
T
4
A
5
/A
6
/Z
7
B
8
/B