Application examples
Operating Manual PNOZ ms4p
22109-EN-03
25
10
Application examples
10.1
Example without position control
Evaluation of bit: "Unfeasible or single-channel signal from the incremental
encoder", without position control
Diagnostic
bit 10: "Unfeasible or single-channel signal from the incremental encoder" must
be evaluated in the user program during operation in such a way that a set bit leads to a
safety-related error reaction (shutdown).
The connection point "Input Device OK" must be incorporated into the application and eval-
uated in such a way that a shutdown occurs if the connection point "Input Device OK"= 0.
10.2
Example with position control
Evaluation of bit: "Unfeasible or single-channel signal from the incremental
encoder", with position control
Diagnostic bit 10: "Unfeasible or single-channel signal from the incremental encoder" may
be set during position control as a result of jitter on the encoder.
The set bit can be tolerated, i.e. evaluated in the user program in such a way that a shut-
down will not occur if the following conditions are met:
}
An additional position control signal must be provided from an external control system
(e.g. PLC) and
}
The signal must have the following status conditions:
– Position control: Signal status = 1
– Operation: Signal status = 0
During operation, diagnostic bit 10 must be evaluated in the user program in such a way
that a set bit leads to a safety-related error reaction (shutdown).