8.2
Testing the safe pulse disabler
8
Operation
8-4
8.2
Testingthesafepulsedisabler
8200
Testingthesafepulsedisabler
8-
Sicherheit_Impulssperre_S1
ThesafetycardmeetstherequirementsofEN IEC 61508uptoSIL 3
andEN ISO 13849-1uptoPL e.
ToachievecategorySIL3orPLe,theoperatormustensurethatthe
functionofthesafepulsedisableristestedperiodically,after8hoursat
thelatest,bytriggeringsafetyfunctionsSS1orSTO:
ByrestartingaftersafetyfunctionsSS1orSTOhavebeentriggered
asaconditionofoperation
or
ByrestartingaftersafetyfunctionSS1hasbeentriggeredbytheop-
erator
Betrieb_Impulssperre_Test
Totestthesafepulsedisabler,proceedasfollows:
Betrieb_Neustart_S1
1.Switchinput"SS1Activate"or"SS1SIL3/Reset"to0 V
ThesafetycardperformsthesafetyfunctionSS1(SafeStop1)and
switchestoa"STOP"condition.The"FAULT"LEDflashes.
2.Switchinput"SS1Activate"or"SS1SIL3/Reset"to24V.
Thesafetycardswitchestoa"STARTUP"condition.Thedeviceand
thesafepulsedisableraretested.The"RUN"LEDflashes.
Thesafetycardswitchestoa"RUN"condition.The"RUN"LEDislit
continuously.
t
1
:Atleast2ms;timeduringwhichSS1ActivateorSS1SIL3/Reset
musthavea"0"signal
t
2
:Approx.2s,safetycard'srun-uptime
SS1Activate:InputforsafetyfunctionSS1
SS1SIL3/Reset:InputforSIL3andreset
STOAcknowledge:OutputforfeedbackfromsafetyfunctionSTO
"RUN"LED:Systemisready
SS1 SIL3/Reset
1
0
1
0
1
0
1
0
SS1 Activate
STO Acknowledge
LED "RUN"
t2
t
t1