P2HZ X4P
Operating Manual P2HZ X4P
20076-EN-08
16
Relay outputs
777354
777355
787354
787355
Utilisation category
of auxiliary contacts
AC15 at
230 V
230 V
230 V
230 V
Max. current
2,5 A
2,5 A
2,5 A
2,5 A
DC13 (6 cycles/
min) at
24 V
24 V
24 V
24 V
Max. current
1,5 A
1,5 A
1,5 A
1,5 A
Utilisation category
in accordance with
UL
Voltage
240 V AC G. P.
240 V AC G. P.
240 V AC G. P.
240 V AC G. P.
With current
5 A
5 A
5 A
5 A
Voltage
24 V DC Resistive
24 V DC Resistive
24 V DC Resistive
24 V DC Resistive
With current
5 A
5 A
5 A
5 A
Pilot Duty
B300, R300
B300, R300
B300, R300
B300, R300
External contact
fuse protection,
safety contacts
In accordance
with the standard
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
Max. melting in-
tegral
100 A²s
100 A²s
100 A²s
100 A²s
Blow-out fuse,
quick
6 A
6 A
6 A
6 A
Blow-out fuse,
slow
4 A
4 A
4 A
4 A
Blow-out fuse, gG
6 A
6 A
6 A
6 A
Circuit breaker
24V AC/DC, char-
acteristic B/C
4 A
4 A
4 A
4 A
External contact
fuse protection, aux-
iliary contacts
Max. melting in-
tegral
100 A²s
100 A²s
100 A²s
100 A²s
Blow-out fuse,
quick
4 A
4 A
4 A
4 A
Blow-out fuse,
slow
2 A
2 A
2 A
2 A
Blow-out fuse, gG
4 A
4 A
4 A
4 A
Circuit breaker 24
V AC/DC, charac-
teristic B/C
2 A
2 A
2 A
2 A
Conventional
thermal current
5 A
5 A
5 A
5 A
Contact material
0,2 µm
Au
0,2 µm
Au
0,2 µm
Au
0,2 µm
Au