P2HZ X4P
Operating Manual P2HZ X4P
20076-EN-08
15
Relay outputs
777354
777355
787354
787355
Number of output
contacts
Safety contacts
(N/O), instantan-
eous
3
3
3
3
Auxiliary contacts
(N/C)
1
1
1
1
Max. short circuit
current IK
1 kA
1 kA
1 kA
1 kA
Utilisation category
In accordance
with the standard
EN 60947-4-1
EN 60947-4-1
EN 60947-4-1
EN 60947-4-1
Utilisation category
of safety contacts
AC1 at
240 V
240 V
240 V
240 V
Min. current
0,01 A
0,01 A
0,01 A
0,01 A
Max. current
5 A
5 A
5 A
5 A
Max. power
1250 VA
1250 VA
1250 VA
1250 VA
DC1 at
24 V
24 V
24 V
24 V
Min. current
0,01 A
0,01 A
0,01 A
0,01 A
Max. current
5 A
5 A
5 A
5 A
Max. power
125 W
125 W
125 W
125 W
Utilisation category
of auxiliary contacts
AC1 at
240 V
240 V
240 V
240 V
Min. current
0,01 A
0,01 A
0,01 A
0,01 A
Max. current
2,5 A
2,5 A
2,5 A
2,5 A
Max. power
600 VA
600 VA
600 VA
600 VA
DC1 at
24 V
24 V
24 V
24 V
Min. current
0,01 A
0,01 A
0,01 A
0,01 A
Max. current
2,5 A
2,5 A
2,5 A
2,5 A
Max. power
60 W
60 W
60 W
60 W
Utilisation category
In accordance
with the standard
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
Utilisation category
of safety contacts
AC15 at
230 V
230 V
230 V
230 V
Max. current
2,5 A
2,5 A
2,5 A
2,5 A
DC13 (6 cycles/
min) at
24 V
24 V
24 V
24 V
Max. current
1,5 A
1,5 A
1,5 A
1,5 A