PNOZ X10.1
Operating Manual PNOZ X10.1
20005-EN-10
| 18
Conventional thermal current
while loading several contacts
774746
774749
Ith per contact at UB DC;
AC1: 240 V, DC1: 24 V
Conv. therm. current with 1 con-
tact
–
8 A
Conv. therm. current with 2 con-
tacts
–
8 A
Conv. therm. current with 3 con-
tacts
–
7 A
Conv. therm. current with 4 con-
tacts
–
6,1 A
Conv. therm. current with 5 con-
tacts
–
5,4 A
Conv. therm. current with 6 con-
tacts
–
5 A
Times
774746
774749
Switch-on delay
With automatic start typ.
180 ms
190 ms
With automatic start max.
250 ms
250 ms
With automatic start after power
on typ.
230 ms
200 ms
With automatic start after power
on max.
320 ms
300 ms
With manual start typ.
200 ms
200 ms
With manual start max.
250 ms
250 ms
With monitored start typ.
150 ms
165 ms
With monitored start max.
200 ms
220 ms
Delay-on de-energisation
With E-STOP typ.
20 ms
20 ms
With E-STOP max.
30 ms
30 ms
With power failure typ.
300 ms
300 ms
With power failure max.
400 ms
400 ms
Recovery time at max. switching
frequency 1/s
After E-STOP
50 ms
50 ms
After power failure
450 ms
450 ms
Min. start pulse duration with a
monitored start
50 ms
50 ms
Supply interruption before de-ener-
gisation
150 ms
150 ms
Environmental data
774746
774749
Climatic suitability
EN 60068-2-78
EN 60068-2-78
Ambient temperature
Temperature range
-10 - 55 °C
-10 - 55 °C
Storage temperature
Temperature range
-40 - 85 °C
-40 - 85 °C