PSEN cs5.1 M12/8
Operating Manual PSEN cs5.1 M12/8
1003419-EN-06
34
Times
Switch-on delay
after UB is applied
1 s
Inputs typ.
1 ms
Inputs max.
3 ms
Actuator typ.
30 ms
Actuator max.
50 ms
Delay-on de-energisation
Inputs typ.
2 ms
Inputs max.
4 ms
Actuator typ.
30 ms
Actuator max.
40 ms
Risk time in accordance with EN 60947-5-3
150 ms
Supply interruption before de-energisation
20 ms
Simultaneity, channel 1 and 2 max.
∞
Environmental data
Ambient temperature
In accordance with the standard
EN 60068-2-14
Temperature range
-25 - 70 °C
Max. at max. operating height
+60 °C
Max. at max. operating height <2000 m
+70 °C
Storage temperature
In accordance with the standard
EN 60068-2-1/-2
Temperature range
-40 - 85 °C
Climatic suitability
In accordance with the standard
EN 60068-2-30
Humidity
93 % r. h. at 40 °C
Max. operating height above sea level
4000 m
EMC
EN 60947-5-3
Vibration
In accordance with the standard
EN 60947-5-2
Frequency
10 - 55 Hz
Amplitude
1 mm
Shock stress
In accordance with the standard
EN 60947-5-2
Acceleration
30g
Duration
11 ms
Airgap creepage
Overvoltage category
III
Pollution degree
3
Rated insulation voltage
75 V
Rated impulse withstand voltage
1 kV
Protection type
Housing
IP66, IP67