PSEN cs5.1 M12/8
Operating Manual PSEN cs5.1 M12/8
1003419-EN-06
29
[10] Sensing face of the actuator, labelled with Pilz logo
[11] Distance from the front edge of the sensor to the limit of the response range (position
if the gate end stop) = 15.9 mm
[12] Distance from the rear edge of the sensor to the limit of the response range (position
if the gate end stop) = 10.5 mm
Procedure:
1. Drill holes (for M4 screws) in the mounting surface to secure the actuator and sensor
(see
).
2. Use a screw to fix the sensor to the mounting surface.
Make sure that the sensor marking that is be used for operation can be operated using
the actuator from the right side.
3. Do not fully tighten the second screw on the safety switch.
4. Use a screw to fix the actuator to the mounting surface.
Make sure that the actuator with the marking (triangle) points towards the marking on
the sensor.
5. Do not fully tighten the second screw on the actuator.
6. Align the safety switch and tighten the screws.
7. Align the actuator and tighten the screws.
Use in operating heights higher than 2000 m above sea level
When using the PSEN cs5.1 M12/8 note the reduced max. ambient temperature of +60 °C
at a height of 2000 m to 4000 m.
Adjustment
}
The stated operating distances (see
) only apply when the
safety switch and actuator are installed facing each other in parallel. Operating dis-
tances may deviate if other arrangements are used.
}
Note the maximum permitted lateral and vertical offset (see
).