CAUTION!
Possible loss of the safety function by changing the release distance

S

ar

 with non-flush installation

Installing the safety switch non-flush within electrically or magnetically con-
ductive material, the value for the assured release distance 

S

ar

 can change.

– Check the assured release distance 

S

ar.

}

Safety switches and actuators must be positioned so that they are secured against a
change of position.

}

The safety switch and actuator should only be secured using screws and nuts made of
non-magnetic material (e.g. brass or stainless steel).

}

Avoid the risk of damages from foreseeable external influences by attaching the safety
switch and actuator. If necessary, safety switch and actuator have to be protected.

INFORMATION

Protect the actuator from unauthorised removal (e.g. via a screw lock or
concealed installation) and from contamination.

}

Prevent self-loosening of the fastening elements of safety switch and actuator.

}

The fastening of safety switch and actuator has to be sufficiently stable to ensure the
proper operation of the safety switch and the actuator.

}

The distance between two safety switches must be maintained (see 

Technical

details [

 17]

).

}

Safety switches and actuators

– Should be kept away from iron swarf
– Should not be exposed to strong magnetic fields

}

Prevent the safety switch and actuator being exposed to heavy shock or vibration.

}

Make sure that the safety switch and actuator cannot be used as an end stop.

}

Circumvention of the safety switch in a reasonably foreseeable manner must be preven-
ted.

}

Please note the installation measures in accordance with EN ISO 14119 for a proximity
switch type 4 with coding level Low.

}

Alignment errors of the guard must not adversely affect the safety function of the guard.

}

The assured operating distance S

ao 

and the assured release distance S

ar 

must be tested

under real conditions.

}

Do not apply any installation tools (e.g. Pliers) on the surfaces of the switch.

}

Install safety switch and actuator

– facing each other in parallel
– so that the faces with the product names are opposite each other.

}

The protection type (see 

Technical details [

 17]

) can only be achieved by using the

Pilz connection leads available as an accessory.

Summary of Contents for 506 404

Page 1: ...PSEN ma2 1p 34 Operating Manual 22192 EN 07 PSEN sensor technology...

Page 2: ...nta tion will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Internet...

Page 3: ...y 6 Disposal 7 For your safety 7 Unit features 7 Function description 8 Block diagram 8 Operating distances 9 Lateral and vertical offset 9 Wiring 10 Pin assignment 10 Requirements and connection to e...

Page 4: ...particularly important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive...

Page 5: ...see Requirements and connection to evaluation devices 11 and when used in series connections of the interface PSEN i1 The safety switch is designed for applications in single or series connections In...

Page 6: ...mbled installed programmed commissioned operated maintained and decommissioned by competent persons A competent person is a qualified and knowledgeable person who because of their train ing experience...

Page 7: ...tuators are replaced with substitute actuators the ori ginal actuators must be destroyed before disposal Do not remove the connector s protective cap until you are just about to connect the unit This...

Page 8: ...losed the safety contacts of the safety switch are closed and the LED will go out The safety switch can be used in series connections Operate the PSEN ma2 1p 34 in conjunction with the following compo...

Page 9: ...ance The offset independent values for the switching distances are included in the Technical details 17 Lateral and vertical offset 1 2 Legend 1 Lateral offset 2 Vertical offset Actuator PSEN 2 1 10 T...

Page 10: ...ck the cross circuit detec tion function Ensure that the safety switch s electrical connections cannot work loose Protect the safety switch s electrical connections from corrosion The safety contacts...

Page 11: ...rating manual for the evaluation device Make sure that the connection is made in accordance with the specifications in the operating manual for the selected evaluation device Defined properties of eva...

Page 12: ...1 33 34 32 41 43 44 42 1 2 3 4 11 12 14 13 1 2 3 4 21 22 24 23 1 2 3 4 31 33 34 32 1 2 3 4 41 43 44 42 24 V I0 0 I0 1 I0 2 I0 3 24 V 0 V PSEN i1 PLC PSENmag Evaluation device Input circuit Input circu...

Page 13: ...D I1 Input OSSD T1 T2 Test pulse outputs Non Ex area Ex area 1 2 3 4 PSENmag 3 1 2 4 11 12 13 14 S21 S22 S11 S12 PNOZ s3 PSEN i1 brown white blue black Installation CAUTION Potential loss of safety fu...

Page 14: ...and actuator has to be sufficiently stable to ensure the proper operation of the safety switch and the actuator The distance between two safety switches must be maintained see Technical details 17 Saf...

Page 15: ...only apply when the safety switch and actuator are installed according to the specifications Installation 13 Operating distances may deviate if other arrangements are used Note the maximum permitted l...

Page 16: ...valuation device Always test the function with single connections with a connected evaluation device The safety function may only be checked by qualified personnel Refer to the notes on checking the s...

Page 17: ...ge 24 V Internal resistance 100 Ohm Max switching current safety contacts 10 mA Max permitted total power dissipation 170 mW Times Reaction time actuator removed 2 ms Environmental data ATEX certifica...

Page 18: ...etition accuracy switching distances 6 Min distance between safety switches 25 mm Sensor flush installation in accordance with EN 60947 5 2 Yes follow installation guidelines Connection type M8 4 pin...

Page 19: ...mm 512 110 Accessories Cable Product type Connection 1 Connection 2 Length Order no PSEN Kabel Winkel cable angleplug 2m Female connector M8 angled 4 pin Open cable end 2 m 533 110 PSEN Kabel Gerade...

Page 20: ...Connector Product type Features Order no PSEN ma adapter Adapter for connecting the safety switch to PSS67 and PDP67 380 300 Series connection Product type Features Order no PSEN i1 Interface for 4 P...

Reviews: