RSE METER
Use and Maintenance Manual
PM Version
ENGLISH
ISV065UTE
Rev.8
Date of issue
04/06/2014
Revision
8
Revision date
20/07/2015
Page 10 of 32
4. Main functions
4.1. On-off
valve
With reference to the standards of the series UNI/TS 11291, RSE implements in particular the following services:
UNI/TS 11291-1 4.3.4 Service: Supply management
UNI/TS 11291-6 6 Flow on/off
The gas flow on/off valve is located within the body of the meter into the inlet connection and is not accessible without causing
permanent damage to the meter itself.
The purpose of the valve is to intercept the gas flow towards the user exclusively for the commercial purposes.
In no way or condition,
the valve has to be considered and used as a useful device to assure safety conditions in the user's plant in case of possible
or patent gas leakages.
The valve is specifically designed to assure its performance and functioning for at least 15 years and it is able to provide the control
microprocessor with the actual status of the valve (closed/open) and with information about its correct operation.
The valve can be closed:
Due to a remote control sent via wireless communication channel (e.g.: from the SAC Remote Management Center);
When changing the battery is not authorized;
Due to a break-in attempted beyond the threshold;
When there is no communication for a configurable time;
When the residual battery power is below the critical level;
In case of failure of the Gdm system.
The previously closed valve, can be opened
only locally
by activating the keyboard according to a special procedure (see chapter
4.1.1)
The opening of the previously closed valve must be authorized
in advance
by the SAC - Control Center.
It is possible to display the status of the valve in the related SV menu (see chapter 6 and chapter 7.1.18).
To reactivate a previously closed valve, RSE must have first of all received the "authorization for opening" from the Control Center.
4.1.1. Procedure for opening the valve through the user interface
After receiving permission for opening the valve from SAC, with a set time window useful to perform such operation and the maximum
number of possible attempts, under the
SV
valve menu the following will appear on the display:
VAL 40 r
valve enabled to be opened
Press
ENTER
to access the submenu.
Under the
VP
menu, the message
PSSD (password requested)
appears;
press
ENTER
to enter the four digits of the password to be
entered (the operator must have the password).
Use the up and down buttons to select the digit to be set, once the desired digit is displayed, press
ENTER
to confirm it. Repeat the
same operation for all four digits.
After selecting the last digit and having pressed
ENTER
, press again
ENTER
to start the opening of the valve.
At the end of the occurred opening the display shows the message "
SUCCESS
".
Under the
SV
menu, the display will show:
VAL 00 A
open valve
4.2. Digital
outputs
RSE does not have any digital outputs
4.3. Data
recording
With reference to the standards of the series UNI/TS 11291, RSE implements in particular the following services:
UNI/TS 11291-1 4.3.3 Service: Dynamic multi-rate capacity
UNI/TS 11291-1 4.3.7 Service: Metering and load profiles
UNI/TS 11291-6 5 Detection and recording of data