MANUALE TECNICO MT035
TECHNICAL MANUAL MT035
25
Taratura apparecchiature di un gruppo costituito
da Regolante tipo Dixi + Sfioro
TAB. 7:
Setting the apparatuses in a plant consisting
of Regulator Dixi + Slam-shut + Relief valve
Taratura Regolatore
Taratura
Taratura
Taratura
(Pas) mbar
SFIORO
BLOCCO Max
BLOCCO Min
Regulator set-point
Set-point
Set-point
Set-point
(Pas) mbar
RELIEF VALVE
SLAM-SHUT Max
SLAM-SHUT Min
6<Pas
≤
12
12<Pas
≤
15
15<Pas
≤
19
19<Pas
≤
24
24<Pas
≤
30
30<Pas
≤
60
60<Pas
≤
80
80<Pas
≤
140
140<Pas
≤
200
200<Pas
≤
500
500<Pas
≤
800
800<Pas
≤
1000
1000<Pas
≤
2500
2500<Pas
≤
5000
5000<Pas
≤
6000
20 mbar
Pas x 1.6
Pas x 1.4
Pas x 1.25
Pas x 1.15
Pas x 1.1
25 mbar
Pas + 20 mbar
Pas + 35 mbar
Pas + 50 mbar
Pas + 70 mbar
Pas x 1.46
Pas x 1.5
Pas x 1.2
6800 mbar
Blocco non
disponibile
Slam-shut not
available
10 mbar
Pas -10 mbar
Pas -20 mbar
Pas -40 mbar
Pas x 0.6
Pas x 0.625
Pas x 0.65
Pas x 0.7