OPERATION
3-10
/ Husky 12 Foam System
© 2017 Pierce Manufacturing Inc. All Rights Reserved.
3-5.
Manual Mode (Manual Water Flow)
This mode of operation is the NFPA required manual override. This mode is used to activate the foam pump without
the flowmeter operating.
Figure
3-9:
Manual Water Flow Mode
1557C, 1562, 1563
1.
While in the normal run screen, press the PAGE button to go to the MODE SELECT screen.
2.
While in the MODE SELECT screen, toggle the UP/DOWN arrows to highlight “Manual Water Flow”.
3.
Press the ENTER button, which will bring up a warning screen, giving you a second chance to continue with the
manual water flow choice, or revert back to the previous auto water flow mode. An alternate method would be
to set the GPM to a fixed rate and adjust the percentage of foam.
In this mode, the foam pump will run regardless of water flow. If discharges are closed, these lines may
be charged to over 300 PSI. At least one discharge or manifold drain must be open before entering this
mode.
In this mode, there are no interlocks, controls, or specific steps required. Use additional caution when
operating in the manual mode. Failure to comply may result in injury or damage to equipment.