EMS-LTE User Manual
Input Type:
The user can choose the input type for related channel. Includes: Counter,
Arm/Disarm, NC, NO, Change and Disabled.
1)
Disabled:
Not use this channel.
2)
NC:
For connecting Normal close type detector, open will alarm.
3)
NO
: For connecting normal open type detector, close will alarm.
4)
Change
: For connecting normal open or normal close type detector, once the
status changed, will be treated as alarm.
5)
Counter
: DIN0 as a high-speed pulse counter, sampling frequency: 1MHz; DIN1~3
as low-speed pulse counter, anti-shake time can be set 1~2000ms, default 1ms;
Need to tick up the Pulse Counter box to setup initial value and interval alarm
value and total alarm value. E.g.: contact a PIR sensor to count how many people
pass through the ATM machine and so on.
6)
Arm/Disarm:
Only the Second Channel (DIN1) can be used as Arm/Disarm
Switch. For connecting a pulse output type switch to Arm or Disarmed the EMS-
LTE.
Alarm SMS:
Under Arm or 24h status, once triggered will send this SMS content to
authorized numbers.
Recovery SMS:
Under Arm or 24h status, if tick the "Recovery Alarm", when triggered
digital input recovery normal will send this SMS content to authorize number.
Change SMS:
Under Arm or 24hr status, only when digital input choose "Change" type,
once action will send this SMS to authorize number.
Current Status:
Stands for input’s current status.
Alarm Verify Time:
Stands for when the digital input Close or Open last time more than
this value, will be treated as a true alarm, if less than this value, then will not alarm.
Siren:
Tick it stands for while this digital input triggering, the DO that output type was
setup as
Siren
will execute its output parameters.
24Hr:
Tick it stands for no matter the EMS-LTE is in Arm or Disarmed mode, this digital
input triggered will alarm.
Initial Value:
When DIN0 as counter, the value begins to count.
Interval Alarm Value:
DIN0 as counter, under Arm or 24hr status, when counter value
arrive "Interval Alarm Value" will send SMS to authorize numbers.
Total Alarm Value:
When counter value arrive "Total Alarm Value", will automatically
refresh it to "Initial Value". Under Arm or 24hr status, will call and SMS to authorize
number.
Step Alarm SMS:
When step alarm, will send this SMS to authorize number.
Total Alarm SMS:
When arrive total max value, will send this SMS to authorize number.