Incorrect temperature readings:
Problem
Possible Cause
Solution
Temperature reads -20°.
Temperature sensor is either
Check wires to temperature sensor
disconnected or has broken
and connect or replace wiring.
wires.
Temperature reads 150°.
Temperature sensor wires touching Verify and correct wiring.
or shorted.
Temperature inaccurate.
Remove the remote temperature
sensor.
Move the sensor to a different
location.
Microphone Problems:
Problem
Possible Cause
Solution
False high sound alarms.
Remote microphone too close
Move assembly or adjust sound
to high sound, unit too sensitive sensitivity. See Chapter 4.
for environment.
Sound alarm not tripping. Remote microphone not close Move remote microphone closer or
enough to high sound, unit
adjust sound sensitivity. See
not sensitive enough.
Chapter 4.
Monitoring Problems:
Problem
Possible Cause
Solution
Alarm status of alert
Incorrect input normality.
Reset input normality. See Chapter 4,
input incorrect.
“Configure Input Normality.”
False power out alarms.
Power recognition time too short. It is common for the power to have
brief interruptions. To prevent a false
alarm, increase the power failure
recognition time. See Chapter 4.
Does not recognize
Battery incorrectly installed
Make sure the battery jumper is
power failure.
or no good.
properly connected to the battery
terminals. See Chapter 2. To verify
proper battery function, unplug unit
and verify continued operation
running on battery only. If the unit
does not work, the battery may need
servicing. Contact Sensaphone
Technical Service Dept.
Unit does not recognize
Inputs disabled for alarm.
Enable the inputs for alarm. See
any alarm.
Chapter 4.
55
Appendix B: Troubleshooting
Summary of Contents for Sensaphone 4100
Page 1: ...SENSAPHONE Model 4100 User s Manual Version 5 41 PHONETICS INC LIT 0006...
Page 6: ...Sensaphone Model 4100 Instruction Manual iv...
Page 30: ...Sensaphone Model 4100 Instruction Manual 28...
Page 38: ...Sensaphone Model 4100 Instruction Manual 36...
Page 42: ...Sensaphone Model 4100 Instruction Manual 40...
Page 54: ...Sensaphone Model 4100 Instruction Manual 52...
Page 60: ...Sensaphone Model 4100 Instruction Manual 58...
Page 62: ...Sensaphone Model 4100 Instruction Manual 60...
Page 66: ...Sensaphone Model 4100 Instruction Manual 64...
Page 67: ...Test Log Test Log 65...