3. Repeat key sequence to change.
To interrogate:
1. Press the WHAT IS key
2. Press the ELECT key
If the power alarm is enabled, the 4100 will simply recite the programmed power
recognition time (see below). If the power alarm is disabled, the 4100 will say “Off ” and
then recite the programmed recognition time.
AC POWER FAILURE RECOGNITION TIME
The power recognition time is the length of time that a power failure must exist
continuously before the Model 4100 will recognize it as an actual alarm and start the dialout
sequence. The default setting is 100 seconds. You may program the power recognition time
from 1 to 199 seconds.
To program the power recognition time:
1. Press the SET key
2. Press the ELECT key
3. Using the number keys, enter the number of seconds
The Model 4100 will recite the digits as they are pressed
4. Press ENTER
The Model 4100 will say “Enter.”
To interrogate:
1. Press the WHAT IS key
2. Press the ELECT key
If the power alarm is enabled (see AC Power Monitoring), the 4100 will recite the
programmed power recognition time. If the power alarm is disabled, the 4100 will say
“Off ” and then recite the programmed power recognition time.
(enter seconds)
33
Chapter 4: Alarm Programming
Summary of Contents for Sensaphone 4100
Page 1: ...SENSAPHONE Model 4100 User s Manual Version 5 41 PHONETICS INC LIT 0006...
Page 6: ...Sensaphone Model 4100 Instruction Manual iv...
Page 30: ...Sensaphone Model 4100 Instruction Manual 28...
Page 38: ...Sensaphone Model 4100 Instruction Manual 36...
Page 42: ...Sensaphone Model 4100 Instruction Manual 40...
Page 54: ...Sensaphone Model 4100 Instruction Manual 52...
Page 60: ...Sensaphone Model 4100 Instruction Manual 58...
Page 62: ...Sensaphone Model 4100 Instruction Manual 60...
Page 66: ...Sensaphone Model 4100 Instruction Manual 64...
Page 67: ...Test Log Test Log 65...