Section 1.  Product Description

The PHS300-x is a room humidity sensor. The PCS300-x is a 
combination temperature and humidity room sensor. The PCS300-x-
DOS has a large LCD display, slider setpoint adjustment, and override 
button. 

Depending on model, the analog outputs are a humidity sensor output 
(defined in the table below), a 10 K

Ω

 type 2 thermistor sensor, 

0-20 K

Ω

 temperature setpoint, and an override contact. All units come 

standard with a 3.5 mm (1/8"), easy access communication jack 
providing direct network access. All PCS units also include an internal 
three position Low/Normal/High test and balance switch. 

Figure 1.  

PHS300-x and PCS300-x sensors only

Figure 2.    

PCS300-x-DOS with display, override, and 

slider temperature setpoint 

Section 2.  General Installation 
Requirements

For proper installation and subsequent operation of each controller, 
pay special attention to the following recommendations:

It is recommended that the sensor(s) be kept at room temperature 
for at least 24 hours before installation to allow any condensation 
that may have accumulated due to low temperature during 
shipping/storage to evaporate.

Upon unpacking the product, inspect the contents of the carton 
for shipping damages. Do not install damaged controllers.

Allow for proper clearance of sensor enclosure, wiring terminals 
and hardware configuration and maintenance.

Each controller is designed to operate under the following 
environmental conditions: 

• Ambient temperature from 32°F to 122°F (0°C to 50°C)
• Relative humidity from 0% to 95%, non-condensing

Ensure proper ventilation of each sensor and avoid areas where 
corroding, deteriorating or explosive vapors, fumes or gases may 
be present. 

Do not drop the sensor or subject it to physical shock.

If the controller is used and/or installed in a manner not specified by 
Phoenix Controls, the functionality and the protection provided by the 
sensor may be impaired.

Model

Humidity Sensor Signal

PHS300-x

Default: 4-20 mA

Field selectable to: 0-5 or 0-10 Vdc

PCS300-x

Default: 4-20 mA

Field selectable to: 0-5 or 0-10 Vdc

PCS300-x-DOS

Default: 4-20 mA

Field selectable to: 0-5 or 0-10 Vdc

CAUTION

Any type of modification to any Phoenix Controls 
product will void the product's warranty.

NOTE

Take special care to keep the front and back plate aligned 
when separating and joining them.

Summary of Contents for PCS300-x

Page 1: ...g recommendations It is recommended that the sensor s be kept at room temperature for at least 24 hours before installation to allow any condensation that may have accumulated due to low temperature d...

Page 2: ...wire through the wall and out of the 1 2 hole leaving about six inches free 6 Pull the wire through the hole in the base plate 7 Secure the base to the drywall anchors using the 6 x 1 inch mounting sc...

Page 3: ...s are possible when AC power wiring is present in the same conduit as the signal lines If you are experiencing any of these difficulties please contact your Phoenix Controls Representative Local and n...

Page 4: ...Terminal Applicable to Option Description OVR1 and OVR2 PCS300 x DOS only O Occupancy override status N O contact output 300 mA 24 Vdc SET1 and SET2 PCS300 x DOS only S Temperature setpoint 0 20 K ou...

Page 5: ...300 mA 30 Vdc SET1 and SET2 PCS300 x DOS only S Temperature setpoint 0 20 K output SEN1 and SEN2 PCS300 x and PCS300 x DOS Temperature sensor 10K 2 thermistor output EXT OVR PCS300 x DOS only D Exter...

Page 6: ...default display shows current temperature toggled every 5 seconds with space humidity When the setpoint slider is moved enough to change the setpoint by 0 5 degrees the setpoint will be displayed as...

Page 7: ...to the first closing of the DO EXT OVR grounded the unit will behave as described in Local Occupancy Override above 2 4 Optional Technicians Adjustments This section details optional adjustments a tec...

Page 8: ...isplay toggles through selections 3 Even when the temperature setpoint is not displayed the terminations SET1 and SET2 are active sending a 0 to 20 K signal out PCS300 x DOS Adjustment Parameters Para...

Page 9: ...emperature Determine that the temperature sensor s wires are connected to the correct controller input terminals and are not loose Check the wires at the sensor and controller for proper connections D...

Page 10: ...Format Default Temperature and Humidity toggled every 5 seconds Temp Setpoint only when slider moved Temp Setpoint Slide pot Cool Warm Down Up Configurable at valve UI Absolute 32 122 F 0 50 C Relativ...

Page 11: ...nction entirely on their own and are not a part of another system or piece of equipment For this reason Phoenix Controls products are exempt from the WEEE Directive Nevertheless Phoenix Controls produ...

Page 12: ...anded 4C Round No Signal 22 Belden 8444 Manhattan M13304 1 White 2 Green 3 Black 4 Red Must be stranded 5C Round No Signal 22 Belden 8445 Manhattan M13305 1 White 2 Brown 3 Black 4 Red 5 Green Must be...

Reviews: