Technical data and ordering data
6959_en_07
PHOENIX CONTACT
83
7.5 V communications power (potential jumper)
Nominal value
7.5 V DC
Tolerance
±5%
Ripple
±1.5%
Maximum output current
2 A DC (protected externally)
Derating
I [A]
0
T [°C]
A
0,5
1,0
1,5
2,0
-25
-15
-5
+5
+25 +35 +45
+55
7062B020
I [A]
Logic current in A
TA [°C]
Ambient temperature in °C
24 V analog supply (potential jumper)
Nominal value
24 V DC
Tolerance
-15% / +20%
Ripple
±5%
Maximum output current
0.5 A DC
Protective measures
Electrical short-circuit protection
INTERBUS
Number of I/O points
8192, maximum
Number of data words
512, maximum
Number of bus segments
254, maximum
Transmission speed
500 kbps or 2 Mbps
Transmission reliability
CR check (Hamming distance: 4)
Protocol
EN 50254
This speed is automatically set according to the connected Inline terminals. Only use terminals with a uniform transmission speed in the overall
connected Inline system (local bus and remote bus).
Number of devices in the INTERBUS system
Total number of bus devices
512, maximum
Number of remote bus devices
254, maximum
Number of PCP devices
62
Number of remote bus levels
16, maximum