System variables and status information
6959_en_07
PHOENIX CONTACT
71
4.1.3
Status register of a PROFINET controller
(ILC 330 PN / ILC 350 PN)
Table 4-2
Variables of the status register for a PROFINET controller
System variable
Type
Meaning
PNIO_SYSTEM_BF
BOOL
No connection to a configured PROFINET device
An error has occurred in the PROFINET network, i.e., a
connection could not be established to at least one
configured device. This value is not set if the “Control BF”
parameter is set to FALSE for a device. This device has
therefore been excluded from connection monitoring.
PNIO_SYSTEM_SF
BOOL
Diagnostic alarm on a configured PROFINET device
At least one PROFINET device is indicating a system error
(diagnostic alarm or maintenance alarm). The error priority
can be determined from the PNIO_DIAG_AVAILABLE,
PNIO_MAINTENANCE_DEMANDED, and
PNIO_MAINTENANCE_REQUIRED variables.
PNIO_DIAG_AVAILABLE
BOOL
Diagnostics available
At least one PROFINET device is indicating a diagnostic
alarm for an active connection. The corresponding
device(s) can be identified using the RALRM diagnostic
block or by requesting the PN_DA_NO_DIAG diagnostic
status byte of each device.
The application must decide, for example, whether outputs
of the other PROFINET devices in the network may
continue to be operated.
PNIO_MAINTENANCE_DEMANDED
BOOL
Maintenance demanded – maintenance demand
At least one PROFINET device is indicating the
“maintenance demand” alarm (high-priority maintenance
alarm) for the active connection. The device can be
identified using the RALRM diagnostic block.
PNIO_MAINTENANCE_REQUIRED
BOOL
Maintenance required – maintenance requirement
At least one PROFINET device is indicating the
“maintenance requirement” alarm (low-priority
maintenance alarm) for the active connection. The device
can be identified using the RALRM diagnostic block.
PNIO_CONFIG_STATUS
WORD
Configuration status of the PROFINET controller
PNIO_CONFIG_STATUS_READY
BOOL
The variable is set if the PROFINET controller has been
initialized correctly. No desired configuration has been
loaded by PC Worx yet.
Summary of Contents for ILC 330 Series
Page 1: ...User manual Installing and operating the ILC 330 and ILC 350 Inline controllers...
Page 8: ...ILC 330 350 8 PHOENIX CONTACT 6959_en_07...
Page 10: ...ILC 330 350 10 PHOENIX CONTACT 6959_en_07...
Page 42: ...ILC 330 350 42 PHOENIX CONTACT 6959_en_07...
Page 68: ...ILC 330 350 68 PHOENIX CONTACT 6959_en_07...